| Plan Review Notes For Permit 06060692 |
| Permit Number |
06060692 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-11 00:00:00 | 1. DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2. DEBRIS SHALL BE REMOVED DAILY FROM | | | THE SITE. | | | | | | 3. EXITS SHALL BE PROVIDED DURING | | | DEMOLITION. | | | | | | 4. SUITABLE EMERGENCY LIGHTS AND EXIT | | | SIGNS SHALL BE PROVIDED TO PROPERLY | | | ILLUMINATE AND IDENTIFY THE MEANS OF | | | EGRESS COMPONENTS. | | | | | | 5. GAS COOKING EQUIPMENT SHALL COMPLY | | | WITH ALL APPLICABLE FIRE CODE | | | REQUIREMENTS. | | | | | | 6. SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE TYPE 1 HOOD IDENTIFIED ON PAGE | | | M1.1. | | | | | | 7. SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE SUPPRESSION SYSTEM PLANNED FOR | | | THE TYPE 1 HOOD. | | | | | | 8. PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATIONS FOR WALLS AND CEILINGS. | | | | | | 9. BUILDING ADDRESS IS REQUIRED. A | | | MINIMUM OF AT LEAST 6" HIGH NUMBERS ARE | | | REQUIRED. | | | | | | 10. IT WAS NOTED THAT THE ROOF MATERIALS | | | WILL MEET CLASS A MATERIALS. | | | | | | 11. EXIT SIGN APPEARS TO BE MISSING FROM | | | SECOND EXIT DOOR. | | | | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|