2006-07-02 00:00:00IN ELEC FOR REVIEW
 **** UNSAT*****
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES
 SHALL BE REFERENCED ON ELECTRICAL PLANS.
 2002 NFPA-70 (NEC), 2002 NFPA-72, 2003
 NFPA-101
  
 2) NOTE: PLEASE SUBMIT A MINIMUM OF TWO
 SETS OF PLANS, UP TO THREE SETS WILL BE
 STAMPED , FOUR SETS WERE SUBMITTED.
 PLEASE SEE NO "POWER" PLANS WAS
 SUBMITTED IN SETS FOR REVIEW?
 215.5,FBC 106.1.2 ADMIN SECT.
  
 3) NOTE: PLEASE SEE 210.8B3 FOR
 REQUIREMENTS OF AREAS IN KITCHEN AND
 AREA OF THE LIKE. PLEASE SEE THIS
 REQUIRES GFI PROTECTION.
  
 4) NOTE: PLEASE SEE THERE APPEARS TO BE
 AN "EQUIPMENT GROUNDING CONDUCTOR" FROM
 METER "CT" TO MAIN "DP". PLEASE SEE
 250.6,250.24B, EQUIPMENT GRNDS ARE ONLY
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
 "OBJECTIONAL CURRENTS AND PARALLELING
 THE NEUTRAL"
  
 5) NOTE: PLEASE SHOW THE LOAD
 CALCULATIONS,
 220.3,220.10,220.11,220.13, ETC.
 PLEASE SHOW ALL CONTINUOUS LOADS AT
 125%,215.3,230.42
  
 6) NOTE: PLEASE SEE VALUE ON PERMIT
 APPLICATION IS LOW FOR TOTAL SCOPE OF
 WORK AS SHOWN ON PLANS. PLEASE SEE FBC
 ADMIN SECT 108.3 WHICH REQUIRES VALUE
 FOR SCOPE PF WORK TO INCLUDE ALL LABOR
 AND MATERIALS EVEN IF ANY MATERIALS ARE
 OWNER SUPPLIED. VALUE MAY BE ADJUSTED BY
 THIS OFFICE USING "MARSHALLS & SWIFT"
 GUIDE AS ADOPTED BY THE FBC SEC ABOVE.
  
 ** PLEASE BE SURE TO COMPLETELY REMOVE
 ANY OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  