2006-07-27 00:00:00DENIED
  
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 2.PERMIT VALUE SHOULD REFLECT THE
 COSTS OF ALL MATERIALS AND LABOR.
 ADJUST PERMIT VALUE OR WE WILL ADJUST IT
 ACCORDING TO MARSHALL AND SWIFT
 ESTIMATING GUIDE. ADDITIONAL PERMIT FEES
 ARE DUE.
  
 3.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 4.PRODUCT APPROVALS REQUIRED FOR
 STANDING SEAM ROOF, BASE UNDERLAYMENT
 FOR METAL ROOF, FLAT ROOF, STRAPS AND
 TIE-DOWNS AND EXTEWRIOR HOLLOW METAL
 DOOR.
  
 5.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 6.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 7.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
 TRUSS DRAWING REQUIRED TO BE APPROVED
 PRIOR TO INSTALLATION.
  
 8.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 9.DOOR CLEARANCES, BATHROOM DOOR TO
 LADIES RESTROOM AND MANAGERS OFFICE
 SHALL HAVE A MINIMUM 18" CLEARANCE AT
 THE LATCH SIDE OF THE DOOR. SEE DIAGRAMS
 AT FBC 11.66.
  
 10.MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS FBC 106.3.5 SHOW THE FOLLOWING
 INFORMATION ON PLANS.
 A. CONSTRUCTION TYPE
 B. OCCUPANCY GROUP
 C. OCCUPANT LOAD
 D. SPRINKLERED OR NOT
 E. CURRENT CODE SECTIONS USED
  
 11.INCLUDE A LIFE SAFTEY PLAN AND
 INCLUDE EXIT ACCESS TRAVEL DISTANCE. FBC
 1015.1
  
 12.SUBMIT TWO ORIGONAL SIGNED AND
 SEALED SURVEYS, FS. 472.025
  
 13.SHOW ACCESSABLE ROUTE FROM PARKING
 AREA INTO THE BUILDING FBC 11.4.3
  
 14.SHOW ROOF AND WALL SHEATHING
 COMPLYING WITH TABLE 2304.9.1 #31 FOR
 THICKNESS AND FASTENING SCHEDULE.
  
 15.A SEPERATE PERMIT IT REQUIRED FOR
 AWNINGS.
  
 16.SHOW SERVICE COUNTERS COMPLYING
 WITH FBC 11-7.2
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  
  