| Notes |
| Date |
Text |
| 2007-01-28 17:20:09 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS | | | WHICH WERE PREVIOUSLY SIZED AT 760AMPS ARE NOW ONLY | | | BEING RATED FOR 510AMPS. PLEASE SEE 240.4, 310.16 AS | | | THESE ARE NOT RATED FOR THE LOAD OR SERVICE ORIGINALLY | | | SUBMITTED. THE MDP IS 800AMPS AND THE PREVIOUS SERVICE | | | ENTRANCE CONDUCTORS WERE RATED FOR 760AMPS. | | | | | | 2) NOTE: PLEASE SEE VOLTAGE DROP CALCULATIONS WERE | | | PREVIOUSLY BASED ON COPPER CONDUCTORS AND OF A | | | DIFFERENT SIZE. PLEASE REVISED CALCULATIONS AS NEEDED. | | | 13-413.1 | | | | | | 3) NOTE: PLEASE SEE PREVIOUS REVIEW AS IT APPEARS THESE | | | BUILDINGS/TRAILERS/SALES CENTER WILL CONTAIN NEW | | | FOOTERS BASED ON NOTES AND REVIEWS BY BUILDING PLANS | | | EXAMINERS AND INSPECTION SERVICES MANAGER. PLEASE | | | PROVIDE REVISIONS TO THE GROUNDING ELECTRODE SYSTEM | | | BASED ON THE NEW FOOTER STEEL WHERE APPLICABLE PER | | | 250.50. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|