Plan Review Notes
Plan Review Notes For Permit 06060672
Permit Number 06060672
Review Stop E
Sequence Number 8
Notes
Date Text
2007-01-28 17:20:09** UNSAT **
  
 1) NOTE: PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS
 WHICH WERE PREVIOUSLY SIZED AT 760AMPS ARE NOW ONLY
 BEING RATED FOR 510AMPS. PLEASE SEE 240.4, 310.16 AS
 THESE ARE NOT RATED FOR THE LOAD OR SERVICE ORIGINALLY
 SUBMITTED. THE MDP IS 800AMPS AND THE PREVIOUS SERVICE
 ENTRANCE CONDUCTORS WERE RATED FOR 760AMPS.
  
 2) NOTE: PLEASE SEE VOLTAGE DROP CALCULATIONS WERE
 PREVIOUSLY BASED ON COPPER CONDUCTORS AND OF A
 DIFFERENT SIZE. PLEASE REVISED CALCULATIONS AS NEEDED.
 13-413.1
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW AS IT APPEARS THESE
 BUILDINGS/TRAILERS/SALES CENTER WILL CONTAIN NEW
 FOOTERS BASED ON NOTES AND REVIEWS BY BUILDING PLANS
 EXAMINERS AND INSPECTION SERVICES MANAGER. PLEASE
 PROVIDE REVISIONS TO THE GROUNDING ELECTRODE SYSTEM
 BASED ON THE NEW FOOTER STEEL WHERE APPLICABLE PER
 250.50.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  