2007-02-06 12:28:10BUILDING PLAN REVIEW
 PERMIT: 06060672
 ADD: 2101 OKEECHOBEE BLVD
 CONT: ROEPNACK CORP
 TEL: (954)444-2995
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)STATE APPROVED PLANS DO NOT SHOW UP ON THE STATE
 WEB SITE, I CALLED THE STATE TO VERIFY THE MDS THIRD
 PARTY LISTING AGENCYS PLAN NUMBER.
 IT APPEARS THESE ARE MODIFICATIONS TO THE STATE
 APPROVED PLANS WHICH WILL NOT SHOW UP ON THE WEB SITE.
 IN DISCUSSING THE PLANS WITH THE PROGRAM DIRECTOR
 MICHAEL ASHWORTH (850) 922-6075 ABOUT WHEN THE THIRD
 PARTY AGENCY MDS PLACES THE DATE OF 1-09-2007 THAT THE
  
 UNIT IS TO BE BUILT TO THE 2004 FBC WITH THE 2005 AND
 2006 FBC REVISIONS.
 2A) THE ISSUE OF THE PLANS INDICATING BEING UNDER THE
 2004 AND THE ASCE 7-98 ARE INCORRECT.
 2B) VARIOUS SHEETS SHEET 3 OF 4 SHOWA 130 WIND SPEED
 INSTEED OF THE CORRECT 140 MILE PER HR HIGHWIND
 DEBRIS REGION.
 2C) PLANS INDICATE A TYPE V BUILDING WHICH REFLECTS THE
 2001FBC OR OLDER. CURRENTLY A TYPE VBUILDING IS A TYPE
 VA OR VB.
 2D) PLANS ALSO DO NOT PROVIDE THE EXPOSURE CATEGORY.
  
 3) THE ISSUE OF THE MANUFACTURED BUILDINGS CAN DEFER
 THE STORM SHUTTERS TO BE INSTALLED AT THE JOBSITE
 (SHEET# 1 NOTE# 16) DOES MEAN THAT IT CAN AND WILL BE
 REVIEWED BY THE LOCAL JURISDICTION.
 PLEASE PROVIDE STATE APPROVALS FOR STORM SHUTTERS:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 THE NEXT ISSUE OF STORM SHUTTERS WILL BETHE WINDOW
 FRAME DESIGN APPROVED BY THE STATE
 DOESN'T PROVIDE FOR SECURING TO THE BOTTOM FRAMING
 MEMBER OR WINDOW SILLWHEN TURNED ON EDGE.
 PLEASE RESPOND HOW CODE COMPLIANCE WILL BE MET?
  
 4) THIS STRUCTURE IS BEING REVIEWED AS A PERMANENT
 STTRUCTURE REQUIRING A FULL FOUNDATION.
 1805.2 DEPTH OF FOOTINGS.
 THE MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED
 GROUND SURFACE SHALL BE 12 INCHES (305 MM). WHERE
 APPLICABLE, THE DEPTH OF FOOTINGS SHALL ALSO CONFORM TO
 SECTIONS 1805.2.1 THROUGH 1805.2.3 .
  
 5) FOUNDATION SHALL BE DESIGNED TO THESE CRITERIA:
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  