| Notes |
| Date |
Text |
| 2006-11-03 19:18:35 | **** NOTESREDLINED *** | | | | | | 1) WIND LOAD CALCULATIONS FOR LT POLES SUBMITTED AND | | | SHALL BE REVIEWED BY THE BUILDING REVIEWER. | | | | | | 2)STATE APPROVED PLANS, RED-LINED, NOT REVIEWED FOR | | | ELECTRICAL CODE COMPLIANCE BY THIS AHJ. ELECTRICAL | | | SERVICE PROVIDED IS NOT THE SAME AS THE VOLTAGE ON THE | | | TRAILERS. 120/240V | | | SERVICE SHEETS RED-LINED, TRAILER VOLTAGE 120/240 | | | WHERE-AS SERVICE IS 120/208V. | | | STATE APPROVED PLANS ARE EXEMPT FROM REVIEW. SERVICE | | | VOLTAGE NOTED, AND RESPONSE FROM TRAILER MANUFACTURE | | | MENTIONS VOLTAGECONSIDERATION WAS TAKEN INTO ACCOUNT | | | AND A/C UNITS/MOTORS LOADS ARE RATED FOR 208V. | | | ANY OF THIS EQUIPMENT IN STATE TRAILER UNITS AREAT | | | OWNERRISK ONLY. | | | | | | ELECTRICAL PLANS STAMPED, IF THERE ARE NAY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICALPLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|