Plan Review Notes For Permit 06060672
Permit Number 06060672
Review Stop E
Sequence Number 3
Notes
Date Text
2006-11-03 19:18:35**** NOTESREDLINED ***
  
 1) WIND LOAD CALCULATIONS FOR LT POLES SUBMITTED AND
 SHALL BE REVIEWED BY THE BUILDING REVIEWER.
  
 2)STATE APPROVED PLANS, RED-LINED, NOT REVIEWED FOR
 ELECTRICAL CODE COMPLIANCE BY THIS AHJ. ELECTRICAL
 SERVICE PROVIDED IS NOT THE SAME AS THE VOLTAGE ON THE
 TRAILERS. 120/240V
 SERVICE SHEETS RED-LINED, TRAILER VOLTAGE 120/240
 WHERE-AS SERVICE IS 120/208V.
 STATE APPROVED PLANS ARE EXEMPT FROM REVIEW. SERVICE
 VOLTAGE NOTED, AND RESPONSE FROM TRAILER MANUFACTURE
 MENTIONS VOLTAGECONSIDERATION WAS TAKEN INTO ACCOUNT
 AND A/C UNITS/MOTORS LOADS ARE RATED FOR 208V.
 ANY OF THIS EQUIPMENT IN STATE TRAILER UNITS AREAT
 OWNERRISK ONLY.
  
 ELECTRICAL PLANS STAMPED, IF THERE ARE NAY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICALPLAN REVIEW