Plan Review Notes
Plan Review Notes For Permit 06060672
Permit Number 06060672
Review Stop E
Sequence Number 2
Notes
Date Text
2006-09-24 00:00:00** UNSAT 2ND REVIEW **
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEW
 THEY ARE SHOWN BELOW WHICH ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
 1) NOTE: OK.
  
 2) NOTE:NO, PLEASE PROVIDE WORST CASE
 ON RECORD SET OF PLANS. IT IS NOTED THAT
 THIS WAS RESPONDED TO IN LTR.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004,
 13-413.1ABC.1 FOR MIN WORST CASE VOLTAGE
 DROP SCENERIO TO BE PROVIDED.
  
 3) NOTE: NO, PLEASE KNOW, THIS COMMENT
 WAS DOE LIGHT POLES WHICH WAS IN COMMENT
 ABOVE. IT IS KNOWN, THAT THIS IS A STATE
 APPROVED TRAILER, AND THE COMMENT WAS
 NOT INTENDED FOR THE WIND LOADS OF THE
 TRAILERS FROM ELECTRICAL REVIEW.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE WIND LOAD
 CALCULATIONS AT THIS TIME. PLANS
 CURRENTLY MENTION THIS IS TO BE
 PROVIDEDS, HOWEVER THIS IS REQUIRED AT
 THIS TIME.
  
 4) NOTE:NO,, NOT CLEAR, IS ALL THE
 PROPOSED SITE LIGHTING WORK GOING TO BE
 UNDER THIS PERMIT ALSO, OR IS THIS ONLY
 FOR THE TEMP SALES CENTER?
  
 ** PREVIOUS REVIEW NOTE **
 ** THIS IS NOT A KAMM CONSULTING
 COMMENT*
 PLEASE SEE THAT THE VALUE SET FORTH ON
 THE PERMIT APPLICATION AND SCOPE OF WORK
 APPLIED FOR DOES NOT SEEMTO INCLUDE
 ALL SITE, SITE LIGHTING, POLES FIXTURES
 AND NEW SALES FACILITY.
 IF ALL THE WORK AS SHOWN SUBMITTED ON
 PLANS IS IN SCOPE (EXCLUDING FUTURE
 BLDGS) THEN PLEASE ADJUST VALUE.
 PLEASE KNOW, IF THE SITE POLE
 CALCULATIONS ARE NOT SUBMITTED AT THIS
 TIME, THEN THE SITE LIGHTING WILL BE
 REQUIRED TO BE UNDER A SEPARATE PERMIT
 WITH PLANS AND FEES ATTHAT TIME.
 FBC ADMINISTRATIVE SECTION 108.3, AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 5) NOTE: OK.
  
 6) NOTE: OK, EQUIPMENT TO BE VERIFIED
 FOR VOLTAGES AS NOTED.
  
 7) NOTE: ?? PLEASE SEE PREVIOUS NOTES ON
 PLANS MENTIONED, NEUTRAL IS NOT TO BE
 BONDED AT TRAILERS, THEREFORE GRND RODS
 WOULD BE REQUIRED WHICH IS WHAT THE
 PREVIOUS COMMENT WAS. PLEASE SEE NOW
 PLANS STILL DO NOT SHOW ANY GROUNDING AT
 THE TRAILERS, AND A NOTE HAS BEEN ADDED
 TO "BOND" NEUTRAL TO THE EQUIPMENT
 GROUNDIGN CONDUCTOR. PLEASE KNOW, IF
 THIS IS DONE THIS WOULD PARALLEL THE
 NEUTRAL WHICH CREATES OBJECTIONABLE
 CURRENT (250.6). PLEASE PROVIDE THE GRND
 RODS AND CWP(IF METAL) AND AS NOTED ANY
 OTHER METAL PIPING AT THE TRAILERS.
 PLEASE REMOVE NOTE #7 AS ANY METAL
 CURRENT CARRYING PARTS FROM TO THE
 TRAILERS MAY BE PRESENT. THIS CAN BE IN
 SUCH OF TELEPHONE/CATV ETC).
 250.32, 250.6
  
 **PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE GROUNDING AT
 TRAILERS AND HOW THESE WILL BE GROUNDED.
 IT SEEMS TO BE SHOWN ON RISER ,HOWEVER
 NO
 CONDUCTORS OR GRND RODS ARE SHOWN AT
 TRAILERS??
 *IT WAS NOTED THAT THE NEUTRAL SHOULD
 NTO BE BONDED AT THE TRAILER.
 250.50,550.16
  
 8) NOTE: OK, AS NOTED HOWEVER PLEASE SEE
 NOTE BAOVE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE IF ANY (METAL )
 CWP TO BE BONDED. PLEASE SEE PLUMB RISER
 WHICH SEEMS TO INDICATE THIS WHICH WILL
 BE REQUIRED.
 PLEASE ALSO KNOW, IF THE TRAILERS BECOME
 REQUIRED TO CONTAIN FIRE SPRINKLERS,
 THEN THIS LINE WOULD ALSO BE BONDED.
 250.50,250.104
  
 9) NOTE: OK, PLEASE BE SURE TO DO THE
 SAME ON THE NEXT REVISED SHEETS.
 THANK YOU.
  
 10) NOTE:NO, SAME NOTE, YES, THESE ARE
 STATE APPROVED TRAILERS, HOWEVER ALL
 STATE APPROVED TRAILERS REVIEWED BY THIS
 OFFICE CONTAING THE CIRCUITING WHICH
 CORRELATES TO THE PANEL SCHEDLULES.
 PLEASE SEE IF THESE PLANS ARE NOT
 AVAILABLE AS MOST ARE.
 PLEASE KNOW, IT IS MOST IMPORTANT, THAT
 THE WIRING FOR THE EM/ EXT LTS IS DONE
 PER 700.12E. IF THE NORMAL LIGHTING GOES
 OUT THE EM/ EXT LTS ARE WIRED AHEAD OF
 THE NORMAL LIGHTING IN ANY ONE AREA. THE
 TRIPPING OF ANY SINGLE OCP DEVICE, SITCH
 ETC SHOULD NOT LEAVE IN ONE AREA IN
 TOTAL DARKNESS.
 NFPA-101, 7.9.2.2
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT THE PLANS FOR
 THE TRAILER SHALL INCLUDE ALL CIRCUITING
 AND CORRELATE WITH PANEL SCHEDULES TO BE
 SUBMITTED.
 PLEASE SEE 700.12E FOR THE CIRCUITING
 THE EM/EXT LTS ON A LOCAL LIGHTING
 BRANCH CIRCUIT.
  
 11) NOTE: OK.
  
 ** NEW NOTE **
  
 12) NOTE: PLEASE BE SURE THAT THE CODES
 AND EDITIONS ARE REFLECTED ON E0.1.
 NFPA-70 2002, NFPA-72 2002 , NFPA-101
 2003.
  
 13) NOTE: PLEASE SEE THE ADDRESS OF 2101
 OKEECHOBEE BLVD IS ASSIGNED TO THIS
 PROJECT, PLEASE ADJUST AND PLACE ON ALL
 TITLE BLOCKS AND PLANS.
 FAC 61G1-16.004,61G15-23.002
  
 ** IMPORTANT**
 OLD SHEETS WERE LEFT IN SETS.
  
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  