Date Text
2006-07-11 00:00:001. PLEASE ILLUSTRATE ALL EXISTING OR NEW
 FIRE HYDRANTS IN THE VICINITY OF THIS
 NEW BUILDING. A NOTE WAS LOCATED ON THE
 SITE PLAN DRAWING INDICATING THAT THE
 FINAL LOCATION OF FIRE HYDRANTS TO BE
 DETERMINED AT TIME OF BUILDING PERMIT
 APPLICATION.
  
 2. PLEASE INDICATE IN WRITING HOW LONG
 THE MODULAR BUILDING WILL BE ON SITE. IS
 IT PERMANANT OR TEMPORARY.
  
 3. BUILDING ADDRESS IS REQUIRED. A
 MINIMUM OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 4. LOCKS ON EXIT DOORS SHALL NOT REQUIRE
 THE USE OF A KEY, TOOL, OR SPECIAL
 KNOWLEDGE FROM THE INTERIOR OF THE
 BUILDING.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709