| Plan Review Notes For Permit 06060672 |
| Permit Number |
06060672 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-11 00:00:00 | 1. PLEASE ILLUSTRATE ALL EXISTING OR NEW | | | FIRE HYDRANTS IN THE VICINITY OF THIS | | | NEW BUILDING. A NOTE WAS LOCATED ON THE | | | SITE PLAN DRAWING INDICATING THAT THE | | | FINAL LOCATION OF FIRE HYDRANTS TO BE | | | DETERMINED AT TIME OF BUILDING PERMIT | | | APPLICATION. | | | | | | 2. PLEASE INDICATE IN WRITING HOW LONG | | | THE MODULAR BUILDING WILL BE ON SITE. IS | | | IT PERMANANT OR TEMPORARY. | | | | | | 3. BUILDING ADDRESS IS REQUIRED. A | | | MINIMUM OF AT LEAST 6" HIGH NUMBERS ARE | | | REQUIRED. | | | | | | 4. LOCKS ON EXIT DOORS SHALL NOT REQUIRE | | | THE USE OF A KEY, TOOL, OR SPECIAL | | | KNOWLEDGE FROM THE INTERIOR OF THE | | | BUILDING. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|