Plan Review Notes
Plan Review Notes For Permit 06060672
Permit Number 06060672
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-06 00:00:00**** UNSAT ***
  
 1) NOTE: PLEASE PROVIDE ENERGY CALCS FOR
 EXTERIOR LIGHTING. PLEASE SEE FBC 2004
 CHAPTER 13,13-415.1.ABC.2 AND PROVIDE
 INFORMATION ACCORDINGLY.
  
 2) NOTE: PLEASE SEE FBC 2004,
 13-413.1ABC.1 FOR MIN WORST CASE VOLTAGE
 DROP SCENERIO TO BE PROVIDED.
  
 3) NOTE: PLEASE PROVIDE WIND LOAD
 CALCULATIONS AT THIS TIME. PLANS
 CURRENTLY MENTION THIS IS TO BE
 PROVIDEDS, HOWEVER THIS IS REQUIRED AT
 THIS TIME.
  
 4) NOTE: ** THIS IS NOT A KAMM
 CONSULTING COMMENT*
 PLEASE SEE THAT THE VALUE SET FORTH ON
 THE PERMIT APPLICATION AND SCOPE OF WORK
 APPLIED FOR DOES NOT SEEMTO INCLUDE
 ALL SITE, SITE LIGHTING, POLES FIXTURES
 AND NEW SALES FACILITY.
 IF ALL THE WORK AS SHOWN SUBMITTED ON
 PLANS IS IN SCOPE (EXCLUDING FUTURE
 BLDGS) THEN PLEASE ADJUST VALUE.
 PLEASE KNOW, IF THE SITE POLE
 CALCULATIONS ARE NOT SUBMITTED AT THIS
 TIME, THEN THE SITE LIGHTING WILL BE
 REQUIRED TO BE UNDER A SEPARATE PERMIT
 WITH PLANS AND FEES ATTHAT TIME.
 FBC ADMINISTRATIVE SECTION 108.3, AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 5) NOTE: PLEASE SEE RISER AND MDP
 SCHEDULE MENTIONS 3-PHASE FEEDS TO
 TRAILER PANELS, YET PANELS IN TRAILERS
 ARE SET UP AS 1-PHASE???
 PLEASE CORRELATE.
 215.5,106.1.2ADMIN SECTION.
  
 6) NOTE: PLEASE ALSO SEE THE VOLTAGE
 INDICATED FOR TRAILERS IS 120/240 AND
 THE SERVICE BEING PROVIDED IS 120/208V.
 PLEASE VERIFY IF ALL VOLTAGES FOR A/C'S
 ETC WILL BE LISTED ETC TO RUN ON 208V.
 ** PLEASE KNOW, THIS WAS JUST AN ISSUE
 ON ANOTHER PROJECT AND THEINSTALLATION
 OF STEP-DOWN TRANSFORMERS FOR ALL
 EQUIPMENT HAD TO BE USED.
 PLEASE VERIFY THIS AND CORRELATE.
 215.5,110.3, ETC
  
 7) NOTE: PELASE PROVIDE GROUNDING AT
 TRAILERS AND HOW THESE WILL BE GROUNDED.
 IT SEEMS TO BE SHOWN ON RISER ,HOWEVR NO
 CONDUCTORS OR GRND RODS ARE SHOWN AT
 TRAILERS??
 *IT WAS NOTED THAT THE NEUTRAL SHOULD
 NTO BE BONDED AT THE TRAILER.
 250.50,550.16
  
 8) NOTE: PLEASE INDICATE IF ANY (METAL )
 CWP TO BE BONDED. PLEASE SEE PLUMB RISER
 WHICH SEEMS TO INDICATE THIS WHICH WILL
 BE REQUIRED.
 PLEASE ALSO KNOW, IF THE TRAILERS BECOME
 REQUIRED TO CONTAIN FIRE SPRINKLERS,
 THEN THIS LINE WOULD ALSO BE BONDED.
 250.50,250.104
  
 9) NOTE: PLEASE SEE THAT PLANS ARE
 "SIGNED" WITH THE LEGAL SIGNATURE KNOWN
 TO THIS OFFICE AND AS ON FILE BY THE
 ENGINEER OF RECORD.
 THE INITIALS AS SHOWN WILL NOT BE
 ACCEPTED.
 FS 471.025, FAC 61G15-23.002
  
 10) NOTE: PLEASE SEE THAT THE PLANS FOR
 THE TRAILER SHALL INCLUDE ALL CIRCUITING
 AND CORRELATE WITH PANEL SCHEDULES TO BE
 SUBMITTED.
 PLEASE SEE 700.12E FOR THE CIRCUITING
 THE EM/EXT LTS ON A LOCAL LIGHTING
 BRANCH CIRCUIT.
  
 11) NOTE: PLEASE CLARIFY THE MEANS OF
 DISCONNECT IN THE TRAILER PANELS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  