| Date |
Text |
| 2006-06-18 00:00:00 | ******UNSAT ****** |
| | |
| | 1) NOTE: PLEASE SEE OWNERSHIP |
| | INFORMATION NEEDS TO BE UPDATED, SEE |
| | NOTES FROM ADDRESSING ETC. |
| | |
| | 2) NOTE: PLEASE SUBMIT ELECTRICAL |
| | PLAN/DRAWING FOR PROPOSED SCOPE OF WORK |
| | TO BE PERFORMED. |
| | PLEASE SEE TWO SEPARATE SHEETS |
| | SUBMITTED, EACH SHEET IS NOT CLEAR. |
| | PLEASE SEE THAT TWO SETS OF ALL SHEETS |
| | ARE REQUIRED. |
| | PLEASE SUBMIT CLEAR AND CONCISE PLANS |
| | WITH AMIN OF DRAFTMAN'S QUALITY. |
| | PLEASE SEE SHEETS WHICH ARE HAND DRAWN |
| | IN PEN ARE NOT PERMITED. |
| | PLEASE SEE FBC 2004 106.3.1, 106.2.1 |
| | ADMIN SEC AS ADOPTED BY CITY OF WEST |
| | PALM BEACH. |
| | |
| | 3) NOTE: PLEASE SEE MIN REQUIREMENT S |
| | FOR SD'S INSIDE AND OUTSIDE ALL SLEEPING |
| | RMS. |
| | NFPA-72 11.5.1.1 |
| | |
| | 4) NOTE: PLEASE SEE MIN CIRCUITING FOR |
| | ARC FAULT PROTECTION OF ANY NEW |
| | ELECTRICAL IN NEW BEDRM.210.12, 2002 |
| | NEC. |
| | |
| | ** AS OTHER ELECTRICAL SHEETS SEEM TO |
| | INDICATE ALL NEW ELECTRICAL WIRING, |
| | PLEASE SUBMIT COMPLETE PLANS, PANEL |
| | SCHEDULES WITH ALL MIN CIRCUITS, |
| | CONDUCTOR SIZES, OCP ETC. |
| | 215.5 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | *** PLEASE KNOW NOC, SHOWS NEW OWNER, |
| | YET SYSTEM SHOWS SOMEONE ELSE. |