| Plan Review Notes For Permit 06060604 |
| Permit Number |
06060604 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-14 00:00:00 | * IT HAS BEEN BROUGHT TO OUR ATTENTION | | | THAT THE JOB AT 7701 MARTIN AVE. DID NOT | | | HAVE CENTRAL AIR CONDITIONING, BUT HAD | | | WINDOW A/C UNITS, THEREFORE THE | | | DESCRIPTION OF WORK TO BE DONE AS "EXACT | | | CHANGE OUT " WAS NOT CORRECT. | | | PLEASE BE ADVISED THAT FALSIFIED | | | DOCUMENTS MAY BE SENT TO THE STATE OF | | | FLORIDA DBPR . | | | | | | *** PERMIT DENIED *** | | | 1) PLEASE SUBMITMANUAL J CALCULATIONS, | | | PER 2004 FBC 13-607.1.ABC.1 . | | | | | | 2) SHOW LOCATION OF CONDENSER UNIT, AND | | | DRAIN LINE ON MECHANICAL PLANS. | | | | | | 3) LABEL ALL ROOMS (KITCHEN, BEDROOM, | | | BATHROOM, ECT.) | | | | | | 4) NEED JOB ADDRESS ON PLANS. | | | | | | 5) ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE PRINTED NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE DESIGN. PER FBC 104.2.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|