2006-07-07 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE A DISONNECTING MEANS
 IS REQUIRED FOR THE FEEDERS COMING FROM
 THE GENERATOR AT THE MAIN HOUSE GROUPED
 WITH THE NEW MAIN OF THE SE RATED ATS.
 PLEASE SEE THIS DISCONNECT DOES NOT
 REQUIRE OCP AND IS ONLY A DISCONNECTING
 MENAS. THIS MAY BE LOCATED ON THE LOAD
 SIDE OF THE ATS OUTSIDE WITH ATS OR ON
 THE LINE SIDE OF THE ATS FROM THE GEN.
 225.31-225.39,
  
 2) NOTE: PLEASE INDICATE HOW THE GEN IS
 BEING BOLTED DOWN AND ATTACHED TO SLAB.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW