Plan Review Notes
Plan Review Notes For Permit 06060589
Permit Number 06060589
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-23 00:00:00******* UNSAT ***********
  
 1) NOTE: PLEASE SEE LOAD CALCULATIONS
 ARE BEING REFERENCE TO 250.82 WHICH IS
 NOT IN THE 2002 NEC WHICH IS WHAT WE ARE
 UNDER.
 215.5
  
 2) NOTE: PLEASE SEE MISSING EUIPMENT
 GROUNDING CONDUCTORS.
 250.24B,250.110,250.122
  
 3) NOTE: PLEASE SEE THE NEW ATS, SHALL
 BE "SERVICE ENTRANCE RATED" AND CONTAIN
 A MCB WHICH MEETS 230.2,230.70,230.76,
 230.79. PLEASE SEE OTHER NEW DISCONNECT
 SHALL BE GROUPED AND LOCATED AT THE SAME
 LOCATION AND MEETING 225.31-225.39
  
 SPECS AS SUBMITTED AND MARKED AR NOT
 ACCEPTABLE FOR INSTALLATION AS SHOWN.
  
 4) NOTE: PLEASE SEE THAT MANUFACTURES
 SPECS/CUT SHEETS SHALL INDICATE ALL MIN
 CLEARENCES AROUND EQUIPMENT.
 110.26, 215.5
 FBC 106.2.1
  
 5) NOTE: PLEASE SEE THAT THIS PROPOSED
 GEN IS LOCATED IN A FLOOD ZONE AND SHALL
 BE INSTALLED A MIN OF 6" ABOVE BFE.
 PLEASE KNOW, THIS IS REQUIRED TO BE
 INDICATE ON PLANS AND PLEASE KNOW,
 BEFORE A FINAL ELECTRICAL INSPECTION AN
 ELEVATION CERTIFICATE SHALL BE GIVEN TO
 THE INSPECTOR AND FILED ON RECORD.
  
 6) NOTE: PLEASE SEE THAT ALL PLANS AND
 DESIGN SHALL CONTAIN THE PRINTED NAME
 AND SIGNATURE OF THE PERSON TAKING
 RESPONSIBILITY OF PLANS AND DESIGN.
 FBC 106.2.1, 106.3.2
  
  
 7) NOTE: PLEASE SEE BUIDLIGN REVIEW
 COMMENTS AS A SLAB DETAIL WAS NOT
 SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]