Text |
| 2006-06-23 00:00:00 | ******* UNSAT *********** |
| | |
| | 1) NOTE: PLEASE SEE LOAD CALCULATIONS |
| | ARE BEING REFERENCE TO 250.82 WHICH IS |
| | NOT IN THE 2002 NEC WHICH IS WHAT WE ARE |
| | UNDER. |
| | 215.5 |
| | |
| | 2) NOTE: PLEASE SEE MISSING EUIPMENT |
| | GROUNDING CONDUCTORS. |
| | 250.24B,250.110,250.122 |
| | |
| | 3) NOTE: PLEASE SEE THE NEW ATS, SHALL |
| | BE "SERVICE ENTRANCE RATED" AND CONTAIN |
| | A MCB WHICH MEETS 230.2,230.70,230.76, |
| | 230.79. PLEASE SEE OTHER NEW DISCONNECT |
| | SHALL BE GROUPED AND LOCATED AT THE SAME |
| | LOCATION AND MEETING 225.31-225.39 |
| | |
| | SPECS AS SUBMITTED AND MARKED AR NOT |
| | ACCEPTABLE FOR INSTALLATION AS SHOWN. |
| | |
| | 4) NOTE: PLEASE SEE THAT MANUFACTURES |
| | SPECS/CUT SHEETS SHALL INDICATE ALL MIN |
| | CLEARENCES AROUND EQUIPMENT. |
| | 110.26, 215.5 |
| | FBC 106.2.1 |
| | |
| | 5) NOTE: PLEASE SEE THAT THIS PROPOSED |
| | GEN IS LOCATED IN A FLOOD ZONE AND SHALL |
| | BE INSTALLED A MIN OF 6" ABOVE BFE. |
| | PLEASE KNOW, THIS IS REQUIRED TO BE |
| | INDICATE ON PLANS AND PLEASE KNOW, |
| | BEFORE A FINAL ELECTRICAL INSPECTION AN |
| | ELEVATION CERTIFICATE SHALL BE GIVEN TO |
| | THE INSPECTOR AND FILED ON RECORD. |
| | |
| | 6) NOTE: PLEASE SEE THAT ALL PLANS AND |
| | DESIGN SHALL CONTAIN THE PRINTED NAME |
| | AND SIGNATURE OF THE PERSON TAKING |
| | RESPONSIBILITY OF PLANS AND DESIGN. |
| | FBC 106.2.1, 106.3.2 |
| | |
| | |
| | 7) NOTE: PLEASE SEE BUIDLIGN REVIEW |
| | COMMENTS AS A SLAB DETAIL WAS NOT |
| | SUBMITTED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |