2006-06-23 00:00:00********* UNSAT ***********
  
 1) NOTE: PLEASE SEE ZONING COMMENTS AS
 NO SITE /SURVEY PLANS WERE SUBMITTED.
 MUST SHOW LOCATION OF GEN WITH ALL
 DIMENSIONS FROM HOUSE ETC.
 PLEASE SEE MECH COMMENTS ALSO.
 ** PLEASE SEE THE FOLLOWING COMMENT, AND
 PLEASE BE SURE MANUFACTURES SPECS/CUT
 SHEETS INDICATE THE MIN CLEARENCE
 REQUIRED AROUND EQUIPMENT IN ALL
 DIRECTIONS.
 215.5
  
 2) NOTE: PLEASE SHOW LOCATION OF ALL
 EQUIPMENT ON A LAYOUT FOR HOUSE ETC .
 PLEASE SEE MISSING DISCONNECT FOR
 FEEDERS COMING FROM GEN AS REQUIRED PER
 225.31-225.39.
  
 3) NOTE: PLEASE PROVIDE PANEL SCHEDULE
 FOR NEW PANEL. 408.4.
 PLEASE PROVIDE ALL INTENDED LOADS FOR
 THIS PANEL.
 220, 215.5, 702.5
  
 4) NOTE: PLEASE COMPLETE RISER DIAGRMA
 WIHT ALL NEW CONDUCTORS AND OCP DEVICES
 BEING INSTALLED TO FEED NEW PANEL.
 215.5, 240.4,310.16 ETC.
  
 5) NOTE: PLEASE SUBMIT ALL MANUFCATURES
 /SPECS/CUT SHEETS ON PANEL/ATS AND
 GENERATOR.
  
 6) NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 AS NO SLAB DETAIL WAS SUBMITTED
 INDICATING TIE DOWN/VIBRATION ETC.
  
 7) NOTE: PLEASE SEE VALUATION IS BASED
 ON ALL LABOR AND MATERIALS WHETHER OR
 NOT ANY EQUIPMENT IS OWNER SUPPLIED.
 VALUE IS BASED ON ALL NEW PERMANANTLY
 INSTALLED EQUIPMENT ETC.
 FBC 108.3, ADMINISTRATIVE SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  