| 2006-08-25 00:00:00 | *** UNSAT2ND REVIEW *** |
| | |
| | ** PLEASE SEE NOTES FROM PREVIOUS |
| | REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE PLANS LAYOUT DOES |
| | NOT CLEARLY SHOW THE LOCATIO OF THE ATS |
| | AND IF THE NEW MAIN LOATED IN THE ATS IS |
| | LOCATED AND GROUPED WITH THE EXISTING |
| | ELECTRICAL PANEL WHICH CONTAINS A MAIN |
| | DISCONNECT. |
| | PLEASE SEE IF THE ATS AS SPECIFIED IS |
| | GOING TO BE INSTALLED AND THIS ATS IS |
| | OUTSIDE AND THE MCB PANEL IS INSIDE, A |
| | DISCONNECT FOR THE FEEDERS COMING FROM |
| | THE GEN WILL BE REQUIRED GROUPED WITH |
| | THE NEW MAIN OUTSIDE. THIS CAN BE DONE |
| | WITH A DISCONNECT RATED FOR THE LOAD |
| | SERVED, NO OCP IS REQUIRED, OR PLEASE |
| | SEE THAT GENERAC NOW ALSO MANUFACTURES A |
| | NEW ATS TO MEET THIS NEED. (RTSE) WHICH |
| | CONTAINS TWO CIRCUITS BREAKERS. ONE |
| | WHICH PROVIDES A DISCONNECT OF THE |
| | POWERE FROM FPL AND THE OTHER WHICH |
| | DISCONNECTS THE FEEDERS FROM THE |
| | GENERATOR. GENERAC IS MAKING THESE AS |
| | CODE HAS MADE A DIFFERENCE IN THEIR |
| | MANUFACTURING PRACTICES. |
| | |
| | PLEASE REVISE PLANS. |
| | |
| | 2) NOTE: PLEASE CORRELATE PLANS |
| | SUBMITTED SHOWING THE SET BACK OF GEN |
| | AND THE SETBACK WHICH IS SHOWN ON |
| | SITE/SURVEY. |
| | PLEASE SEE ONE SHOWS 12FT AND THE OTHER |
| | 9FT. |
| | |
| | 3) NOTE: PLEASE SEE FS 713.13(2) AS THE |
| | NOC SUBMITTED WHICH WAS RECORDED ON |
| | 5/23/06 HAS SINCE EXOIRED. PLEASE KNOW |
| | NOC'S ARE ONLY VALID FOR 90DAYS UNLESS |
| | WORK HAS COMMENCED. PLEASE RE-RECORD THE |
| | NOC BEFORE PICKIGN UP PERMIT. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |