| Date |
Text |
| 2006-07-23 00:00:00 | *** UNSAT *** |
| | |
| | ** PLEASE KNOW, AS THE ELECTRICAL SHEET |
| | ALSO CONTAINS THE PLUMB AND PLUMB RISER, |
| | THE PLUMB WILL BE RE-STAMPED ONCE |
| | ELECTRICAL REVIEW IS OK.. |
| | |
| | ** PLEASE SEE SOME NOTES ARE NEW BASED |
| | ON REVISED PLANS SUBMITTED ALONG WITH |
| | NOTE FROM PREVIOUS REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE THAT ALL |
| | PLANS/DESIGN NOT REQUIRED TO BE DONE BY |
| | AN ARCHITECT OR ENGINEER ARE STILL |
| | REQUIRED TO CONTAIN THE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | PLANS AND DESIGN. |
| | 106.1.2 FBC ADMIN SECT. |
| | |
| | 2) NOTE: PLEASE STILL SEE MISSING LAYOUT |
| | FOR SD'S IN EXISTING DWELLING . PLEASE |
| | SEE ALL EXISTING SLEEPING RMS ARE |
| | REQUIRED. QUOTING THE CODE IS NOT |
| | PERMITTED IN LEIU OF SHOWING DETAIL. |
| | R313, NFPA-72 11.5.1.1 |
| | |
| | 3) NOTE: PLEASE SEE GFI CIRCUIT NOW |
| | SHOWN AS 15A, #14 WITH 1920 VA? MAX 1440 |
| | VA PERMITTED, PLEASE ADJUST. |
| | 240.4,310.16 |
| | |
| | 4) NOTE: PLEASE SEE NEW A/C WALL UNIT |
| | WILL ALSO REQUIRED ARC FAULT PROTECTION |
| | AS MANY WALL A/C UNITS DO NOT CONTAIN |
| | ARC FAULT PROTECTION. THERE ARE SOME |
| | UNITS ON THE MARKET WITH AFCI |
| | PROTECTION, HOWEVER CIRCUIT WILL REQUIRE |
| | PROTECTION. |
| | 210.12B |
| | PLEASE SEE OTHER BEDRM CIRCUIT AS "FAULT |
| | PROTECTION" IS THIS A MISPRINT FOR ARC |
| | FAULT? |
| | |
| | 5) NOTE: PLEASE SEE RISER INDICATES |
| | FEEDERS TO NEW 60A SUB PANEL THROUGH |
| | "OFFSET NIPPLE" , HOWEVER PLEASE SEE |
| | PANEL ON PLANS IS BEING SHOWN ON THE |
| | OTHER SIDE AND ON ANOTHER WALL. AN |
| | "OFFSETT NIPPLE" IS NOT POSSIBLE. |
| | PLEASE SEE CONDUCTORS AND MAX PIPE FILL |
| | IN TABLES OF CHAPETR 9. PLEASE ADJUST |
| | CONDUIT. (IF PVC, MUST USE SCH 80). |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |