| 2006-06-24 00:00:00 | ***** UNSAT ******* |
| | |
| | 1) NOTE: PLEASE CORRLEATE PANEL(S) AND |
| | RISER. |
| | PLEASE SEE EXSITING 125A PANEL IS ALSO |
| | BEING SHOWN AS 200A'S? |
| | PLEASE SEE THERE ARE TWO SEPARATE PANEL |
| | SCHEDULES SUBMITTED ONE SEEMS TO BE THE |
| | EXISTING IN MAIN HOUSE, BUT THE OTHER IS |
| | NOT LABLED? IF IT IS THE NEW PANEL |
| | SCHEDULE AT METER/MAIN THEN, PLEASE SEE |
| | MISSING 125A SUB-FEED TO EXISTING PANEL? |
| | THIS SI UNCLEAR AT THIS TIME AND LOAD |
| | CALCULATIONS CAN NOT BE VERIFIED. |
| | 215.5,220.31B ETC. |
| | |
| | 2) NOTE: PLEASE SEE NEW BATH CIRCUIT IS |
| | SHOWN AS 240V /2-POLE. BRKR.? |
| | PLEASE ADJUST. |
| | 215.3 |
| | |
| | 3) NOTE: PLEASE SEE MISSIGN RECEPT PER |
| | 210.52 ON WALL IN BEDRM. |
| | |
| | 4) NOTE: PLEASE SEE NOTES ON ELECTRICAL |
| | AND BUILDING SHEETS WITH RESPECT TO |
| | EXISTING BUILDINGS AND SD'S ARE FROM THE |
| | 2001 FBC. |
| | PLEASE SEE THE NEW FBC 2004 HAS AN |
| | ENTIRE BOOK ON ITS OWN FOR EXISTING |
| | DWELLINGS. PLEASE ALSO SEE THE NEW |
| | RESIDENTIAL CODE 2004. |
| | SD'S ARE STILL REQUIRED BASED ON |
| | ALTERATIONS, ADDTIONS, AND THE NEW R313, |
| | HOWEVER PLEASE ALSO SEE REFERENCE FOR |
| | SD'S HAS NOW CHANGED AS THE NFPA-72 |
| | CODES QUOTED ARE FROM THE PREVIOUS CODE. |
| | PLEASE SEE THESE ARE PER 11.5.1.1, |
| | 11.8.3 2002 NFPA-72. THE 1999 WAS |
| | CHAPTER 8 AS STATED. |
| | PLEASE ADJUST AND PLEASE SHOW SD |
| | LOCATIONS INSIDE AND OUTSIDE ALL |
| | SLEEPING ROOMS. |
| | |
| | 5) NOTE: PLEASE SEE MIN OCP FOR 10KW |
| | HEAT ON AHU SHOULD BE SIZED AT 125% PER |
| | 424.3B. (60A'S). |
| | |
| | 6) NOTE: PLEASE SHOW LOCATION OF NEW |
| | SERVICE ON PLANS ALONG WITH PANEL |
| | LOCATION. |
| | 230.70,230.2, 215.5,240.24,408.7 ETC |
| | |
| | ** PLEASE BE SURE TO COMPLETELY REMOVE |
| | ANY OLD VOIDED SHEETS AND ONLY INSERT |
| | NEW REVISED SHEETS INTO TWO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | ** ONE COPY OF OLD/VOIDED SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |