Plan Review Notes
Plan Review Notes For Permit 06060561
Permit Number 06060561
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-24 00:00:00***** UNSAT *******
  
 1) NOTE: PLEASE CORRLEATE PANEL(S) AND
 RISER.
 PLEASE SEE EXSITING 125A PANEL IS ALSO
 BEING SHOWN AS 200A'S?
 PLEASE SEE THERE ARE TWO SEPARATE PANEL
 SCHEDULES SUBMITTED ONE SEEMS TO BE THE
 EXISTING IN MAIN HOUSE, BUT THE OTHER IS
 NOT LABLED? IF IT IS THE NEW PANEL
 SCHEDULE AT METER/MAIN THEN, PLEASE SEE
 MISSING 125A SUB-FEED TO EXISTING PANEL?
 THIS SI UNCLEAR AT THIS TIME AND LOAD
 CALCULATIONS CAN NOT BE VERIFIED.
 215.5,220.31B ETC.
  
 2) NOTE: PLEASE SEE NEW BATH CIRCUIT IS
 SHOWN AS 240V /2-POLE. BRKR.?
 PLEASE ADJUST.
 215.3
  
 3) NOTE: PLEASE SEE MISSIGN RECEPT PER
 210.52 ON WALL IN BEDRM.
  
 4) NOTE: PLEASE SEE NOTES ON ELECTRICAL
 AND BUILDING SHEETS WITH RESPECT TO
 EXISTING BUILDINGS AND SD'S ARE FROM THE
 2001 FBC.
 PLEASE SEE THE NEW FBC 2004 HAS AN
 ENTIRE BOOK ON ITS OWN FOR EXISTING
 DWELLINGS. PLEASE ALSO SEE THE NEW
 RESIDENTIAL CODE 2004.
 SD'S ARE STILL REQUIRED BASED ON
 ALTERATIONS, ADDTIONS, AND THE NEW R313,
 HOWEVER PLEASE ALSO SEE REFERENCE FOR
 SD'S HAS NOW CHANGED AS THE NFPA-72
 CODES QUOTED ARE FROM THE PREVIOUS CODE.
 PLEASE SEE THESE ARE PER 11.5.1.1,
 11.8.3 2002 NFPA-72. THE 1999 WAS
 CHAPTER 8 AS STATED.
 PLEASE ADJUST AND PLEASE SHOW SD
 LOCATIONS INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS.
  
 5) NOTE: PLEASE SEE MIN OCP FOR 10KW
 HEAT ON AHU SHOULD BE SIZED AT 125% PER
 424.3B. (60A'S).
  
 6) NOTE: PLEASE SHOW LOCATION OF NEW
 SERVICE ON PLANS ALONG WITH PANEL
 LOCATION.
 230.70,230.2, 215.5,240.24,408.7 ETC
  
 ** PLEASE BE SURE TO COMPLETELY REMOVE
 ANY OLD VOIDED SHEETS AND ONLY INSERT
 NEW REVISED SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ** ONE COPY OF OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  