| Date |
Text |
| 2006-10-05 00:00:00 | |
| | |
| | |
| | DENIED |
| | |
| | PREVIOUS REVIEW NOTES NOT ADDRESSED: |
| | |
| | 1) OK |
| | |
| | 2) OK VALUE ADJUSTED AND INCREASED |
| | PERMIT FEES ARE DUE ($255.16) |
| | |
| | 3) OK FEES ADDED TO PERMIT FEES |
| | |
| | 4) OK |
| | |
| | 5) OK |
| | |
| | 6) THE PERMIT APPLICATION SHALL INCLUDE |
| | TWO COPIES OF EACH PRODUCT APPROVAL THAT |
| | IS RELEVANT PER 9B-72. THESE SHOULD |
| | INCLUDE THE FLORIDA STATE APPROVAL COVER |
| | PAGES, AND THE PRODUCT NOA THAT LISTS |
| | THE SYSTEM COMPONENTS/ FASTENER LIST |
| | PAGES, THE PAGES WITH THE CHOSEN |
| | ASSEMBLY/ SYSTEM TO BE USED AND THE |
| | GENERAL LIMITATIONS PAGE. ALL CAN BE |
| | FOUND ON WWW.FLORIDABUILDING.ORG |
| | |
| | ******NO STATE OF FLORIDA COVER PAGES |
| | WERE SUBMITTED PLEASE SEE ABOVE WEB SITE |
| | FOR THE STATE OF FLORIDA PRODUCT |
| | APPROVAL COVER SHEETS******* |
| | PLEASE KNOW THE CITY OF WEST PALM BEACH |
| | REQUIRES THE FLORIDA STATE PRODUCT |
| | APPROVAL COVER SHEETS WHEN AVAILABLE. |
| | THEY CAN BE SEARCHED FOR ON |
| | WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE |
| | AND NOT SUBMITTED APPLICATIONS WILL BE |
| | DENIED |
| | |
| | 7) THE FOLLOWING INFORMATION IS NEEDED |
| | OR MISSING FROM THE PRODUCT APPROVALS |
| | |
| | A) WHERE APPLICABLE THE BUILDING |
| | OFFICIAL REQUIRES THE STATE OF FLORIDA |
| | PRODUCT APPROVALS COMPLETE WITH STATE |
| | COVER SHEET AND APPLICABLE NOA |
| | |
| | ********SEE ABOVE NOTE******** |
| | |
| | B) OK |
| | |
| | C) CHOOSE ASSEMBLY THAT WILL BE USED IN |
| | ROOFING NOA (PG.5 OR 6) ALSO SEE THAT |
| | THEY WILL NOT MEET THE PRESSURES |
| | REQUIRED FOR ZONES 2 & 3 OF ROOF WITHOUT |
| | ENHANCED FASTENING. LIMITATION #7 ALLOWS |
| | FOR THIS BUT THE CALCULATIONS SHALL BE |
| | PREPARED SIGNED AND SEALED BY A DESIDGN |
| | PROFFESIONAL. (SEE PG. 7 LIMITATION#7) |
| | |
| | ******PROVIDE ENGINEERS CALCULATIONS FOR |
| | THE ENHANCED FASTENING IN THE CORNER, |
| | ZONE 3******* |
| | |
| | D) WINDOWS ARE IMPACT RESISTANT BUT |
| | DOORS ARE NOT AND WILL REQUIRE IMPACT |
| | PROTECTION, IF USING THESE DOORS PROVIDE |
| | PRODUCT APPROVAL FOR SHUTTERS |
| | |
| | ******THE JELD WEN PRODUCT APPROVAL IS |
| | FOR A GLAZED NON IMPACT DOOR, PLEASE |
| | PROVIDE AN APPROVED IMPACT RESISTANT |
| | PRODUCT APPROVALFOR THE DOOR |
| | |
| | E) PROVIDE PRODUCT APPROVALS FOR PRECAST |
| | CONCRETE LINTELS |
| | |
| | ******NOT SUBMITTED****** |
| | |
| | 7) OK |
| | |
| | 8) PROVIDE A LINTEL SCHEDULE, TYPICAL |
| | DETAIL PAGE 2 WILL NOT WORK AS TOP OF |
| | BEAM AT 8'-0" AND DOOR AND WINDOWS AT |
| | 6'-8" TO TOP. TOTAL 16" LESS 8" BOND |
| | BEAM LEAVES 8" AND DETAIL SHOWS |
| | 16"LINTEL |
| | |
| | *******NOT CHANGED ON THE DRAWING******* |
| | |
| | 9) OK, REMOVED FROM DRAWING |
| | |
| | 10) PROVIDE CORRECT ROOF COVERING ON |
| | DRAWINGS AND SPECIFY THE NAILING PATTERN |
| | PER FASTENING TABLE 2304.9.1 FBC |
| | |
| | ******NOT ADDRESSED ON THE DRAWING***** |
| | |
| | 11) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |
| | ******PER 713.13(2) F.S. |
| | IF THE IMPROVEMENT DESCRIBED IN THE NOC |
| | HAS NOT COMMENCED WITHIN 90 DAYS OF |
| | RECORDING THE NOTICE IS VOID PLEASE |
| | RERECORD NOC ******** |
| | |
| | |
| | NEW NOTES: |
| | |
| | 1) PER 106.1.3 FBC* THE BUILDING |
| | OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, STANDARDS FOR PLANS |
| | AND SPECIFICATIONS "NO WHITE OUT, PENCIL |
| | OR INK" |
| | |
| | |
| | NOTE: FBC = FLORIDA BUILDING CODE 2004 |
| | FBC* = WEST PALM BEACH |
| | ADMINISTATIVE AMMENDMENTS TO FBC |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |