Plan Review Notes
Plan Review Notes For Permit 06060544
Permit Number 06060544
Review Stop P
Sequence Number 6
Notes
Date Text
2007-03-13 15:19:48REVISION: OK, SEE PROVISO
  
 ****************PROVISO****************
 A} PER FBC-2004 PLUMBING, SECTION 917.4 LOCATION: THE
 AIR ADMITTANCE VALVE SHALL BE LOCATED A MINIMUM OF 4
 INCHES ABOVE THE HORIZONTAL BRANCH DRAIN OR FIXTURE
 DRAIN BEING VENTED.
 B} PER FBC-2004 PLUMBING, SECTION 802.1.6 DOMESTIC
 DISHWASHING MACHINES: DOMESTIC DISHWASHING MACHINES
 SHALL DISCHARGE INTO A WYE-BRANCH FITTING ON THE
 TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER
 CONNECTION OF A FOOD WASTE GRINDER.
 C} PER FBC-2004 PLUMBING, SECTION 708.3.5 BUILDING
 DRAIN AND BUILDING
 SEWER JUNCTION: THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.