| 2007-09-12 17:51:11 | |
| | |
| | ** DENIED REVIEW FOR REVISIONS** |
| | |
| | ** PLEASE SEE SOME ITEMS REDLINED ON PREVIOUS PLANS ARE |
| | IN NEED OF CORRECTION. |
| | PLEASE SEE ITEM MISSED ON PREVIOUS REVIEW WHICH IS IN |
| | NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE PANEL SCHEDULE IS SHOWN AS A MLO |
| | (MAIN LUG ONLY ) PANEL YET RISER SHOWS THIS AS MCB(MAIN |
| | CIRCUIT BREAKER). |
| | A MAIN IS REQUIRED PER 230.70, 230.71, PLEASE ADJUST. |
| | |
| | 2) NOTE: PLEASE SEE 424.3B AS THE OVER CURRENT |
| | PROTECTION FOR THE 10KW AIR HANDLER IS REQUIRED TO BE |
| | AT 125%. (60AMP MIN) |
| | |
| | 3) NOTE: PLEASE CLARIFY THE DINING ROOM CIRCUIT AS |
| | SHOWN. IF THIS IS FOR LIGHTING THEN THIS IS OK, HOWEVER |
| | OF THIS CIRCUIT IS FOR THE DINING ROOM RECEPTACLES, |
| | THEN THIS MUST MEET 210.52B1, 210.11C1 AND 220.16. |
| | MUST BE 20AMP, #12 AND 1500 VA FIGURED INTO THE LOAD |
| | CALCULATIONS WITH SMALL APPLIANCE CIRCUITS. |
| | |
| | 4) NOTE: PREVIOUS PLANS CONTAINED THE SMOKE ALARMS AS |
| | REQUIRED PER R313 OF THE FLORIDA RESIDENTIAL CODE AND |
| | NFPA-72 11.5.1.1.1, 11.8.3 HOWEVER THEY HAVE NOW BEEN |
| | REMOVED FROM PLANS. |
| | PLEASE KNOW AS REQUIRED PER SECTIONS AS NOTED ABOVE, |
| | PLEASE PLACE BACK ON PLANS MEETING THE MINIMUM CODE |
| | REQUIREMENTS. |
| | ** PLEASE ALSO KNOW THAT THESE WOULD BE SMOKE ALARMS, |
| | NOT SMOKE DETECTORS AS LISTED ON PANEL SCHEDULE. PLEASE |
| | SEE NFPA-72 DEFINITIONS AS SMOKE DETECTORS ONLY DETECT |
| | AND DO NOT SOUND AN ALARM. |
| | |
| | 5) NOTE: PLEASE SEE KITCHEN COUNTER SPACE WHICH |
| | INDICATES A NEW 60AMP SINGLE PHASE GFI. THIS IS UNCLEAR |
| | WHAT THIS IS. |
| | FBC 106.3.5.4, 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |