Plan Review Notes
Plan Review Notes For Permit 06060544
Permit Number 06060544
Review Stop P
Sequence Number 5
Notes
Date Text
2007-02-14 16:26:10REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY
 OF WEST PALM BEACH AMENDMENTS:
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE ON THE REVISION:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION
 ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
 ******* PLEASE REVISE THE FOLLOWING ON SHEET M2-1
 PLUMBING RISER DIAGRAM:
 A} CLEARLY INDENTIFY THE AIR ADMITTANCE VALVES FOR THE
 SINKS ON SHEET M2-1 PLUMBING RISER DIAGRAM ON THE
 RESUBMITTED REVISION PER FBC-2004 PLUMBING, SECTION
 917.
 B} PLEASE REVISE THE AIR ADMITTANCE VALVES LOCATION
 FOR THE SINKS ON SHEET M2-1 PLUMBING RISER DIAGRAM PER
 FBC-2004 PLUMBING, SECTION 917.4.
 C} CLEARLY INDICATE THE DOUBLE BOWL SINK W/ DISPOAL
 AND DISHWASHER PLUMBING ON SHEET M2-1 PLUMBING RISER
 DIAGRAM ON THE RESUBMITTED REVISION.
  
 ******IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  