2007-03-01 10:02:19** MECHANICAL REVISION **
 *** PROVISO ***
 1)A.H.U. MOUNTING DETAIL SHOWS AREA BETWEEN THE
 SOFFITT AND CEILING TO BE OPEN WHICH WOULD MAKE THAT
 PART OF THE OPEN PLENUM AND WOULD NEED TO COMPLY WITH
 2004 FBC/M 602.2.1 MATERIALS EXPOSED WITHIN PLENUMS,
 ALSO COMPLY WITH2004 FBC/R M1601.10 MECHANICAL
 CLOSETS.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.