| Notes |
| Date |
Text |
| 2007-02-13 11:18:18 | MECHANICAL REVISION | | | *** DENIED *** | | | 1) SEE ELECTRICAL REVIEW NOTE #1, PLEASE CORRECT. | | | | | | 2) SEE MECHANICAL REVISION PAGE M2-1, A.H.U. MOUNTING | | | DETAIL SHOWS AREA BETWEEN THE SOFFITT AND CEILING TO BE | | | OPEN WHICH WOULD MAKE THAT PART OF THE OPEN PLENUM AND | | | WOULD NEED TO COMPLY WITH2004 FBC/M 602.2.1 MATERIALS | | | EXPOSED WITHIN PLENUMS, ALSO SEE 2004 FBC/R M1601.10 | | | MECHANICAL CLOSETS. PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|