| Plan Review Notes For Permit 06060544 |
| Permit Number |
06060544 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-02-12 12:04:36 | *** UNSAT *** | | | | | | 1) NOTE: PLEASE SEE PLANS SUBMITTED CONTAIN *WHITE-OUT8 | | | AND HAND DRAWN CHANGES MADE TO PLANS. THIS IS NOT | | | PERMITTED IN ANY WAY. | | | FS 481.221. | | | | | | 2) NOTE: PLEASE SEE PREVIOUS REVIEWED PLANS WERE | | | REDLINED FOR MISSING NEW FOOTER STEEL REQUIRED AS PART | | | OF THE GROUNDING ELECTRODE SYSTEM.250.50 PLEASE INCLUDE | | | AS PREVIOUSLY REDLINED. | | | | | | 3) NOTE: PLEASE SEE MISSING SMOKE ALARMS PER NFPA-72 | | | 11.5.1.1, 11.8.3. | | | | | | 4) NOTE: PLEASE SEE THE OCP FOR THE 5KW HEAT STRIP | | | SHOWN TOO HIGH, 50A?S ON 5KW? VERIFY AND ADJUST ON | | | PANEL SCHEDULE. | | | THIS WAS REDLINED ON PREVIOUS PLANS TO REVISE. | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|