2007-02-12 12:04:36*** UNSAT ***
  
 1) NOTE: PLEASE SEE PLANS SUBMITTED CONTAIN *WHITE-OUT8
 AND HAND DRAWN CHANGES MADE TO PLANS. THIS IS NOT
 PERMITTED IN ANY WAY.
 FS 481.221.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEWED PLANS WERE
 REDLINED FOR MISSING NEW FOOTER STEEL REQUIRED AS PART
 OF THE GROUNDING ELECTRODE SYSTEM.250.50 PLEASE INCLUDE
 AS PREVIOUSLY REDLINED.
  
 3) NOTE: PLEASE SEE MISSING SMOKE ALARMS PER NFPA-72
 11.5.1.1, 11.8.3.
  
 4) NOTE: PLEASE SEE THE OCP FOR THE 5KW HEAT STRIP
 SHOWN TOO HIGH, 50A?S ON 5KW? VERIFY AND ADJUST ON
 PANEL SCHEDULE.
 THIS WAS REDLINED ON PREVIOUS PLANS TO REVISE.
  
  