2006-11-14 14:35:38UNSAT 3RD TIME
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR
 PLUMBING PLAN REVIEW,PLEASE REFERENCE THE CORRECTED
 SANITARY PLUMBING RISER DIAGRAM ON SHEET M2-1 FOR THE
 RESUBMITTAL:
  
 1. THE TWO WAY CLEANOUT IS STILL INDICATED WRONG ON THE
 SANITARY PLUMBING RISER DIAGRAM ON SHEET M2-1. PLEASE
 CORRECT ON THE RESUBMITTAL.
  
 2. THE DOUBLE BOWL KITCHEN SINK WITH A DISHWASHER ON
 SHEET M2-1 IS STILL INDICATED WRONG ON THE SANITARY
 RISER DIAGRAM. PLEASE CORRECT ON THE RESUBMITTAL.
  
 3. THE STUDOR VENT INDICATED ON SHEET M2-1 IS STILL
 INDICATED WRONG. PER FBC-2004 PLUMBING, SECTION 917.4
 THE STUDOR VENT SHALL BE LOCATED A MINIMUM OF 4" ABOVE
 THE HORIZONTAL DRAIN BRANCH. PLEASE CORRECT ON THE
 RESUBMITTAL.
  
 THE FOLLOWING ARE NEW ITEMS FOUND ON THE RESUBMITTAL
 THAT NEED TO BE CORRECTED ON THE RESUBMITTAL TO MEET
 CODE COMPLIANCE:
  
 4. PLEASE INDICATE THE STANDPIPE ON THE WASHING
 MACHINE. PER FBC-2004 PLUMBING, SECTION 802.4
  
 5. PLEASE CORRECT THE LOCATION OF THE CLEANOUT ON THE
 WASHING MACHINE STACK TO BE FOUR FEET ABOVE FINNISH
 FLOOR (4' AFF). PER FBC-2004 PLUMBING, SECTION 708.9
 ACCESS SHALL BE PROVIDED TO ALL CLEANOUTS.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  