| 2006-11-14 14:35:38 | UNSAT 3RD TIME |
| | REFERENCE: FBC-2004 PLUMBING |
| | |
| | THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR |
| | PLUMBING PLAN REVIEW,PLEASE REFERENCE THE CORRECTED |
| | SANITARY PLUMBING RISER DIAGRAM ON SHEET M2-1 FOR THE |
| | RESUBMITTAL: |
| | |
| | 1. THE TWO WAY CLEANOUT IS STILL INDICATED WRONG ON THE |
| | SANITARY PLUMBING RISER DIAGRAM ON SHEET M2-1. PLEASE |
| | CORRECT ON THE RESUBMITTAL. |
| | |
| | 2. THE DOUBLE BOWL KITCHEN SINK WITH A DISHWASHER ON |
| | SHEET M2-1 IS STILL INDICATED WRONG ON THE SANITARY |
| | RISER DIAGRAM. PLEASE CORRECT ON THE RESUBMITTAL. |
| | |
| | 3. THE STUDOR VENT INDICATED ON SHEET M2-1 IS STILL |
| | INDICATED WRONG. PER FBC-2004 PLUMBING, SECTION 917.4 |
| | THE STUDOR VENT SHALL BE LOCATED A MINIMUM OF 4" ABOVE |
| | THE HORIZONTAL DRAIN BRANCH. PLEASE CORRECT ON THE |
| | RESUBMITTAL. |
| | |
| | THE FOLLOWING ARE NEW ITEMS FOUND ON THE RESUBMITTAL |
| | THAT NEED TO BE CORRECTED ON THE RESUBMITTAL TO MEET |
| | CODE COMPLIANCE: |
| | |
| | 4. PLEASE INDICATE THE STANDPIPE ON THE WASHING |
| | MACHINE. PER FBC-2004 PLUMBING, SECTION 802.4 |
| | |
| | 5. PLEASE CORRECT THE LOCATION OF THE CLEANOUT ON THE |
| | WASHING MACHINE STACK TO BE FOUR FEET ABOVE FINNISH |
| | FLOOR (4' AFF). PER FBC-2004 PLUMBING, SECTION 708.9 |
| | ACCESS SHALL BE PROVIDED TO ALL CLEANOUTS. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |