| Plan Review Notes For Permit 06060544 |
| Permit Number |
06060544 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-11-09 12:30:09 | *** REDLINEDTHE FOLLOWING: | | | | | | | | | NEW FOOTER STEEL REQUIRED AS PART OF THE GROUNDING | | | ELECTRODE SYSTEM.250.50, | | | | | | SA'S PER NFPA-72 11.5.1.1, 11.8.3 | | | | | | OCP FOR THE 5KW HEAT STRIP SHOWN TOO HIGH,50A'S ON | | | 5KW? VERIFY AND ADJUST IN FIELD. | | | REVISE WITH ANY OTHER REVISIONS BEFORE ROUGH. NO NEED | | | TO REVISE OR CORRECT AT THIS TIME. |
|