Plan Review Notes
Plan Review Notes For Permit 06060544
Permit Number 06060544
Review Stop E
Sequence Number 3
Notes
Date Text
2006-11-09 12:30:09*** REDLINEDTHE FOLLOWING:
  
  
 NEW FOOTER STEEL REQUIRED AS PART OF THE GROUNDING
 ELECTRODE SYSTEM.250.50,
  
 SA'S PER NFPA-72 11.5.1.1, 11.8.3
  
 OCP FOR THE 5KW HEAT STRIP SHOWN TOO HIGH,50A'S ON
 5KW? VERIFY AND ADJUST IN FIELD.
 REVISE WITH ANY OTHER REVISIONS BEFORE ROUGH. NO NEED
 TO REVISE OR CORRECT AT THIS TIME.