Plan Review Notes
Plan Review Notes For Permit 06060544
Permit Number 06060544
Review Stop P
Sequence Number 2
Notes
Date Text
2006-10-06 00:00:00******UNSAT******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW:
  
 1. THE TWO-WAY CLEANOUT ON SHEET M2-1 IS
 INDICATED WRONG ON THE SANITARY PLUMBING
 RISER DIAGRAM. PLEASE CORRECT FOR THE
 RESUBMITTAL.
  
 2. THE DOUBLE BOWL KITCHEN SINK WITH
 DISHWASHER ON SHEET M2-1 IS INDICATED
 WRONG ON THE SANITARY PLUMBING RISER
 DIAGRAM. PLEASE CORRECT FOR THE
 RESUBMITTAL.
  
 3. THE STUDOR VENT INDICATED ON THE
 ISLAND SINK ON SHEET M2-1 IS INDICATED
 WRONG. PER FBC-2004 PLUMBING, SECTION
 917.4 THE STUDOR VENT SHALL BE A MINIMUM
 OF 4" ABOVE THE HORIZONTAL BRANCH DRAIN.
  
 4. PER FBC-2004 PLUMBING, SECTION
 106.3.5.4 PLEASE INDICATE THE EXISTING
 KITCHEN RENOVATED INTO A LAUNDRY ROOM
 PLUMBING ON THE SANITARY PLUMBING
 ISOMETRIC RISER DIAGRAM. PLEASE REMEMBER
 THE FOLLOWING WHEN ADDING THE WASHING
 MACHINE PLUMBING TO THE SANITARY
 ISOMETRIC PLUMBING RISER DIAGRAM.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE
 INDIVIDUALLY TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: PLEASE REFERENCE THE
 CORRECTIONS IN RED INK ON SHEET M2-1 ON
 THE ISOMETRIC SANITARY RISER DIAGRAM,
 ONLY ONE CORRECTED DRAWING IN RED INK
 FOR REFERENCE FOR RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  