| Date |
Text |
| 2006-09-26 00:00:00 | ********* UNSAT 2ND REVIEW ********* |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW ARE STILL IN NEED OF ADDRESSING |
| | ALONG WIHT NEW NOTES DUE TO CHANGES IN |
| | PLANS BEING SUBMITTED. |
| | |
| | 1) NOTE: OK, HOWEVER SEE NEW NOTES. |
| | |
| | 2) NOTE:OK, HOWEVER SEE NEW NOTES. |
| | |
| | 3) NOTE: NO, PLEASE SEE NO "SMOKE |
| | DETECTORS" WERE SHOWN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE SD'S REQUIRED IN |
| | EXSITING DWELLING, PER R313. IS DWELLING |
| | CONTAINS EXISTING SD'S WHICH MEET |
| | CURRENT CODE, PLEASE SHOW, OR PLEASE |
| | SHOW NEW SD'S AS REQUIRED INSIDE AND OUT |
| | SIDE ALL SLEEPING ROOMS. |
| | NFPA-72 11.5.1.1,11.8.3 |
| | |
| | 4) NOTE: NO, PLEASE SEE THE SEC'S ARE |
| | NOW BEING SHOWN, HOWEVER PLEASE SEE |
| | THERE ARE NOW "TWO" "EQUIPMENT GROUNDING |
| | CONDUCTORS" BEING SHOWN?? |
| | PLEASE SEE 250.6, 250.24B AS THIS |
| | CREATES OBJECTIONABLE CURRENTS. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE INDICATE THE NEW SEC'S |
| | FROM METER TO NEW DISC. 215.5 |
| | (NO EQUIP GROUNDING CONDUCTOR.) |
| | |
| | 5) NOTE: OK, NEW ARCHITECT. |
| | |
| | |
| | 6) NOTE: NO,PLEASE SEE NO PANEL SCHEDULE |
| | WAS SUBMITTED SHOWING ALL MIN |
| | CIRCUITSING AS REQUIREDL. ARC FAULT FOR |
| | NEW SD'S, AND ALL OTHER NEW CIRCUITS |
| | BEING PROVIDED SHOWING THE OCP DEVICES |
| | AND MIN CONDUCTORS SIZES. |
| | 240.4,408.4,310.16 ETC. |
| | PLEASE ALSO SEE NEW NOTES. |
| | |
| | ** PREVIOUS REVIEW NOTES |
| | |
| | PLEASE VERIFY LOAD OF NEW FRIG, |
| | AS A NEW DEDICATED CIRCUITS IS NOT SHOWN |
| | ON NEW PANEL SCHEDULE FOR THIS.?? |
| | 210.23,24, 210.52B, 210.11C1, 220.16 |
| | ETC. |
| | |
| | 7) NOTE: OK., HOWEVER DUE TO NNOTES NEW |
| | AND EXISTING THESE LOADS MAY CHANGE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE LOADON |
| | EXISTING 200A PANEL. |
| | 215.5 |
| | |
| | ********** NEW NOTES ********* |
| | |
| | 8) NOTE: PLEASE SEE MISSING RECEPTS |
| | ALONG KITCHEN COUNTER SPACE PER |
| | 210.52C1, AND PLEASE BE SURE TO INDICATE |
| | ALL GFI/GFI PROTECTED PER 210.8A6. |
| | |
| | 9) NOTE; PLEASE SEE A NEW 220V RECEPT IS |
| | BEING SHOWN IN THE MIDDLE OF A ROOM |
| | ALONG WITH A DISCONNECT AND GFI, BUT IT |
| | IS UNCLEAR WHAT THESE ARE FOR?? |
| | PLEASE SEE IS THIS THE MISSIGN DISC FOR |
| | THE AHU?. PLEASE ALSO INDICATE WHAT THE |
| | OTHER TWO ARE FOR? |
| | ARE THESE MISPRINTS ON PLANS. |
| | |
| | 10) NOTE: PLEASE SHOW THE NEW CU UNIT |
| | WHICH IS NOT SHOWN ON PLANS. |
| | PLEASE SEE MISSING DISCONNECT PER 440.11 |
| | , AND MISSING GFI (NEW OR EXISTING) PER |
| | 210.63. |
| | |
| | 11) NOTE: PLEASE SEE THERE IS AN OVEN |
| | NOW SHOWN IN LOAD CALCULATIONS, HOWEVER |
| | NOT SHOWN IN KITCHEN LAYOUT. |
| | PLEASE SHOW. |
| | |
| | 12) NOTE: PLEASE SEE "A" SHEET INDICATES |
| | A NEW 60A SUB PANEL AND THERE IS A NOTE |
| | FOR A NEW PANEL ON ELECTRICAL PLANS |
| | HOWEVER THERE IS NO PANEL SCHEDULE |
| | SUBMITTED TO INDICATE THE NEW FEED TO |
| | THIS PANEL FOR OCP, FEEDERS, ETC . |
| | PLEASE PROVIDE A REVISED RISER DIAGRAM |
| | SHOWIGN THIS NEW SUB PANEL.215.5 |
| | PLEASE SEE310.16,240.4, 408.4 ETC. |
| | PLEASE ALSO SEE 100.26 FOR DIRECTION OF |
| | THE FACING OF THE NEW SUB PANEL, AS |
| | KITCHEN COUNTER SPACE IS ON ONE SIDE. |
| | |
| | 13) NOTE: PLEASE INDICATE THE LOCATIONS |
| | OF ALL APPLIANCES, INCLUDING THE |
| | LOCATIONS OF THE NEW DRYER, WASHER ETC. |
| | SEEMS TO BE WHERE THE OLD KITCHEN WAS? |
| | PLEASE INDICATE ALL AREA AND ROOM |
| | DESIGNATIONS ON PLANS. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 14) NOTE: PLEASE VERIFY NEW OR EXSTIGN |
| | DEDICATED DINING RM/ BRKFAST RM CIRCUITS |
| | PER 210.52B1,210.11C1, 220.16. |
| | |
| | |
| | 15) NOTE: PLEASE CORRELATE MECHANICAL |
| | AND ELECTRICAL FOR A/C HEAT LOADS. |
| | PLEASE SEE ONE AT 8KW AND ONE BEING |
| | SHOWN AT 5KW?? |
| | 424.3B, 310.16,240.4 . |
| | |
| | |
| | ** PLEASE KNOW, AS THERE ARE ITEMS NOT |
| | SUBMITTED FOR REVIEW AS PERVIOUSLY |
| | REQUESTED, AND REQUESTED ON THIS REVIEW, |
| | PLEASE KNOW THERE MAY BE A POSSIBILITY |
| | OF NEW COMMENTS ON NEXT REVIEW. |
| | PLANS ARE NOT COMPLETE ATTHIS TIME. |
| | 106.3.5.4 FBC ADMIN SECT. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| 2006-09-24 00:00:00 | IN ELEC FOR REVIEW |