Plan Review Notes
Plan Review Notes For Permit 06060544
Permit Number 06060544
Review Stop E
Sequence Number 2
Notes
Date Text
2006-09-26 00:00:00********* UNSAT 2ND REVIEW *********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW ARE STILL IN NEED OF ADDRESSING
 ALONG WIHT NEW NOTES DUE TO CHANGES IN
 PLANS BEING SUBMITTED.
  
 1) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 2) NOTE:OK, HOWEVER SEE NEW NOTES.
  
 3) NOTE: NO, PLEASE SEE NO "SMOKE
 DETECTORS" WERE SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE SD'S REQUIRED IN
 EXSITING DWELLING, PER R313. IS DWELLING
 CONTAINS EXISTING SD'S WHICH MEET
 CURRENT CODE, PLEASE SHOW, OR PLEASE
 SHOW NEW SD'S AS REQUIRED INSIDE AND OUT
 SIDE ALL SLEEPING ROOMS.
 NFPA-72 11.5.1.1,11.8.3
  
 4) NOTE: NO, PLEASE SEE THE SEC'S ARE
 NOW BEING SHOWN, HOWEVER PLEASE SEE
 THERE ARE NOW "TWO" "EQUIPMENT GROUNDING
 CONDUCTORS" BEING SHOWN??
 PLEASE SEE 250.6, 250.24B AS THIS
 CREATES OBJECTIONABLE CURRENTS.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE INDICATE THE NEW SEC'S
 FROM METER TO NEW DISC. 215.5
 (NO EQUIP GROUNDING CONDUCTOR.)
  
 5) NOTE: OK, NEW ARCHITECT.
  
  
 6) NOTE: NO,PLEASE SEE NO PANEL SCHEDULE
 WAS SUBMITTED SHOWING ALL MIN
 CIRCUITSING AS REQUIREDL. ARC FAULT FOR
 NEW SD'S, AND ALL OTHER NEW CIRCUITS
 BEING PROVIDED SHOWING THE OCP DEVICES
 AND MIN CONDUCTORS SIZES.
 240.4,408.4,310.16 ETC.
 PLEASE ALSO SEE NEW NOTES.
  
 ** PREVIOUS REVIEW NOTES
  
 PLEASE VERIFY LOAD OF NEW FRIG,
 AS A NEW DEDICATED CIRCUITS IS NOT SHOWN
 ON NEW PANEL SCHEDULE FOR THIS.??
 210.23,24, 210.52B, 210.11C1, 220.16
 ETC.
  
 7) NOTE: OK., HOWEVER DUE TO NNOTES NEW
 AND EXISTING THESE LOADS MAY CHANGE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE LOADON
 EXISTING 200A PANEL.
 215.5
  
 ********** NEW NOTES *********
  
 8) NOTE: PLEASE SEE MISSING RECEPTS
 ALONG KITCHEN COUNTER SPACE PER
 210.52C1, AND PLEASE BE SURE TO INDICATE
 ALL GFI/GFI PROTECTED PER 210.8A6.
  
 9) NOTE; PLEASE SEE A NEW 220V RECEPT IS
 BEING SHOWN IN THE MIDDLE OF A ROOM
 ALONG WITH A DISCONNECT AND GFI, BUT IT
 IS UNCLEAR WHAT THESE ARE FOR??
 PLEASE SEE IS THIS THE MISSIGN DISC FOR
 THE AHU?. PLEASE ALSO INDICATE WHAT THE
 OTHER TWO ARE FOR?
 ARE THESE MISPRINTS ON PLANS.
  
 10) NOTE: PLEASE SHOW THE NEW CU UNIT
 WHICH IS NOT SHOWN ON PLANS.
 PLEASE SEE MISSING DISCONNECT PER 440.11
 , AND MISSING GFI (NEW OR EXISTING) PER
 210.63.
  
 11) NOTE: PLEASE SEE THERE IS AN OVEN
 NOW SHOWN IN LOAD CALCULATIONS, HOWEVER
 NOT SHOWN IN KITCHEN LAYOUT.
 PLEASE SHOW.
  
 12) NOTE: PLEASE SEE "A" SHEET INDICATES
 A NEW 60A SUB PANEL AND THERE IS A NOTE
 FOR A NEW PANEL ON ELECTRICAL PLANS
 HOWEVER THERE IS NO PANEL SCHEDULE
 SUBMITTED TO INDICATE THE NEW FEED TO
 THIS PANEL FOR OCP, FEEDERS, ETC .
 PLEASE PROVIDE A REVISED RISER DIAGRAM
 SHOWIGN THIS NEW SUB PANEL.215.5
 PLEASE SEE310.16,240.4, 408.4 ETC.
 PLEASE ALSO SEE 100.26 FOR DIRECTION OF
 THE FACING OF THE NEW SUB PANEL, AS
 KITCHEN COUNTER SPACE IS ON ONE SIDE.
  
 13) NOTE: PLEASE INDICATE THE LOCATIONS
 OF ALL APPLIANCES, INCLUDING THE
 LOCATIONS OF THE NEW DRYER, WASHER ETC.
 SEEMS TO BE WHERE THE OLD KITCHEN WAS?
 PLEASE INDICATE ALL AREA AND ROOM
 DESIGNATIONS ON PLANS.
 FBC 106.1.2 ADMIN SECT.
  
 14) NOTE: PLEASE VERIFY NEW OR EXSTIGN
 DEDICATED DINING RM/ BRKFAST RM CIRCUITS
 PER 210.52B1,210.11C1, 220.16.
  
  
 15) NOTE: PLEASE CORRELATE MECHANICAL
 AND ELECTRICAL FOR A/C HEAT LOADS.
 PLEASE SEE ONE AT 8KW AND ONE BEING
 SHOWN AT 5KW??
 424.3B, 310.16,240.4 .
  
  
 ** PLEASE KNOW, AS THERE ARE ITEMS NOT
 SUBMITTED FOR REVIEW AS PERVIOUSLY
 REQUESTED, AND REQUESTED ON THIS REVIEW,
 PLEASE KNOW THERE MAY BE A POSSIBILITY
 OF NEW COMMENTS ON NEXT REVIEW.
 PLANS ARE NOT COMPLETE ATTHIS TIME.
 106.3.5.4 FBC ADMIN SECT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2006-09-24 00:00:00IN ELEC FOR REVIEW