| 2006-06-24 00:00:00 | ********* UNSAT ********* |
| | |
| | 1) NOTE: PLEASE SEE RISER INDICATES A |
| | NEW DISCONNECT,HOWEVER PLEASE SEE THERE |
| | IS NO INFORMATION WHERE THIS IS, WHAT |
| | SIZE, AIC RATINGS ETC. |
| | 110.9,215.5,230.72 |
| | PLEASE SHOW EXSITING MCB LOCATION AND |
| | LOCATION OF NEW DISC. |
| | |
| | 2) NOTE: PLEASE INDICATE SIZE OF METER, |
| | AS SERVICE IS NOW BEING SHOWN AS 300A'S, |
| | AND METER IF EXISTING 200A'S , IS NOT |
| | ACCEPTABLE. PLEASE SEE SEC'S ARE NOT |
| | SHOWN ON RISER. ARE THESE GOING TO BE |
| | UPGRADES FOR NEW 300A SERVICE? OR ARE |
| | THESE ALREADY RATED FOR 300A'S? |
| | PLEASE SEE 240.4,310.16,310.15B6, ETC |
| | |
| | 3) NOTE: PLEASE PROVIDE SD'S REQUIRED IN |
| | EXSITING DWELLING, PER R313. IS DWELLING |
| | CONTAINS EXISTING SD'S WHICH MEET |
| | CURRENT CODE, PLEASE SHOW, OR PLEASE |
| | SHOW NEW SD'S AS REQUIRED INSIDE AND OUT |
| | SIDE ALL SLEEPING ROOMS. |
| | NFPA-72 11.5.1.1,11.8.3 |
| | |
| | 4) NOTE: PLEASE INDICATE THE NEW SEC'S |
| | FROM METER TO NEW DISC. 215.5 |
| | (NO EQUIP GROUNDING CONDUCTOR.) |
| | |
| | 5) NOTE: PLEASE SEE THAT THE PERSON |
| | RESPONSIBLE FOR PLANS/ DESIGN SHALL |
| | CLEARLY INDICATE THEIR PRINTED NAME AND |
| | SIGNATURE. |
| | FBC 106.1.2, 106.1.3,106.3.4.3 ADMIN |
| | SECT AS ADOPTED BY THE CITY OF WEST PALM |
| | BEACH. |
| | |
| | 6) NOTE: PLEASE VERIFY LOAD OF NEW FRIG, |
| | AS A NEW DEDICATED CIRCUIT IS NOT SHOWN |
| | ON NEW PANEL SCHEDULE FOR THIS.?? |
| | 210.23,24, 210.52B, 210.11C1, 220.16 |
| | ETC. |
| | |
| | 7) NOTE: PLEASE PROVIDE LOADON |
| | EXISTIGN 200A PANEL. |
| | 215.5 |
| | |
| | ** PLEASE BE SURE TO MAKE TWO COMPLETE |
| | SETS FOR REVIEW AND STMAPING. PLEASE |
| | KNOW THAT ALL OLD/VOIDED SHEETS SHOULD |
| | BE COMPLETELY REMOVED FROM SETS AND ONLY |
| | THE NEW REVISED SHEETS SHOULD B INSERTED |
| | INTO THE NEW SETS. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | TO HELP TO AVOID ANY POSSIBLE DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |