| Plan Review Notes For Permit 06060540 |
| Permit Number |
06060540 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-19 00:00:00 | 1. DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2. DEBRIS SHALL BE REMOVED THE SITE | | | DAILY. | | | | | | 3. EXITS ARE TO REMAIN CLEAR AND | | | UNOBSTRUCTED. | | | | | | 4. WRONG LIFE SAFETY CODE NOTED ON PAGE | | | 6 OF 6. SHOULD READ THE FLORIDA FIRE | | | PREVENTION CODE. | | | | | | 5. ENSURE THAT AN EMERGENCY LIGHT | | | FIXTURE IS PRESENT IN THE STORAGE OR | | | EXIT ACCESS TO THE REAR EXIT DOOR. | | | | | | 6. SEPARATE PLANS AND PERMIT REQUIRED | | | FOR FIRE SPRINKLER SYSTEM REMODEL. | | | | | | 7. INTERIOR FINISH ON WALLS AND CEILINGS | | | SHALL MEET APPLICABLE FIRE CODE | | | REQUIREMENTS. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|