2006-06-18 00:00:00****** UNSAT ********
  
 1) NOTE: PLEASE SEE THE NEW SCOPE PF
 WORK INCLUDING 277/480V INSTALLATION
 SHALL BE SIGNED, DATED AND SEALED BY A
 FL P.E.
 471.003(2)(H).
  
 2) NOTE: PLEASE SEE NEW SCOPE OF WORK
 BEING PROPOSED UNDER THE 2004 FBC.
 PLEASE SEE CHAPTER 13,
 13-415-.1.ABC.1.1, .1.2,1.3.
 PLEASE PROVIDE THE CORRECT TYPE OF TC AS
 REQUIRED, PLEASE SUBMIT SCHEDULING,
 LOCAATION OF ALL REQUIRED OVER -RIDE
 DEVICES LOCATED A ENTRNACES TO SPACE, AS
 LIGHTING IS VISABLE TO OCCUPANTS.
 PLEASE KNOW, DEPENDING ON DEVICE CHOSEN,
 EITHGER 30 MAX OR 4HRS MAX ALLOWED FOR
 OVERIDING.
 PLEASE SEE 13-415.1.ABC.3,
 13415.1.AB.1, 13-415.2.ABC.1
 PLEASE PROVIDE LIGHTING CALCS/ENERGY
 CALCS AS REQUIRED ABOVE.
  
 ** IMPORTANT**
 WHEN RESUBMITTING PLANS,PLEASE BE SURE
 TO COMPLETELY REMOVE ANY OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE COPY OF THE REMOVED OLD/VOIDED
 SHEETS SHOULD BE SUBMITTED FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  