| 2006-06-18 00:00:00 | ****** UNSAT ******** |
| | |
| | 1) NOTE: PLEASE SEE THE NEW SCOPE PF |
| | WORK INCLUDING 277/480V INSTALLATION |
| | SHALL BE SIGNED, DATED AND SEALED BY A |
| | FL P.E. |
| | 471.003(2)(H). |
| | |
| | 2) NOTE: PLEASE SEE NEW SCOPE OF WORK |
| | BEING PROPOSED UNDER THE 2004 FBC. |
| | PLEASE SEE CHAPTER 13, |
| | 13-415-.1.ABC.1.1, .1.2,1.3. |
| | PLEASE PROVIDE THE CORRECT TYPE OF TC AS |
| | REQUIRED, PLEASE SUBMIT SCHEDULING, |
| | LOCAATION OF ALL REQUIRED OVER -RIDE |
| | DEVICES LOCATED A ENTRNACES TO SPACE, AS |
| | LIGHTING IS VISABLE TO OCCUPANTS. |
| | PLEASE KNOW, DEPENDING ON DEVICE CHOSEN, |
| | EITHGER 30 MAX OR 4HRS MAX ALLOWED FOR |
| | OVERIDING. |
| | PLEASE SEE 13-415.1.ABC.3, |
| | 13415.1.AB.1, 13-415.2.ABC.1 |
| | PLEASE PROVIDE LIGHTING CALCS/ENERGY |
| | CALCS AS REQUIRED ABOVE. |
| | |
| | ** IMPORTANT** |
| | WHEN RESUBMITTING PLANS,PLEASE BE SURE |
| | TO COMPLETELY REMOVE ANY OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | ONE COPY OF THE REMOVED OLD/VOIDED |
| | SHEETS SHOULD BE SUBMITTED FOR |
| | REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |