Plan Review Notes
Plan Review Notes For Permit 06060507
Permit Number 06060507
Review Stop E
Sequence Number 3
Notes
Date Text
2006-07-23 00:00:00** REDLINED THE FOLLOWING.
  
 MISSING "EQUIPMENT GROUNDING CONDUCTOR"
 AFTER THE FIRST MEANS OF DISCONNECT AND
 FROM GEN TO ATS.
 250.24B,250.110,250.122 ETC.
  
 SIGNAGE REQUIRED FOR NEW SERVICE RATED
 MAIN AND GEN DISCONNECT.
 230.2E, 702.8