2006-07-15 00:00:00******* UNSAT 2ND REVIEW *******
  
 1) NOTE: PLEASE SEE STILL MISSING
 DISCONNECT FOR FEEDERS COMING FROM GEN
 REQUIRED AT HOUSE AND GROUPED WITH THE
 NEW SE RATED ATS WITH MAIN.
 PLEASE KNOW, THE ATS AS SHOWN ONLY
 DISCONECTS POWER FROM THE LINE/FPL SIDE
 AND DEOS NOT DISCONNECT POWWER FROM THE
 GEN FEEDERS.
 PLEASE KNOW THE BRKR ON GEN IS NOT
 ACCEPTABLE FOR THIS.
 225.31-225.39, 110.27ETC.
 PLEASE KNOW, THIS DISCONNECT DOES NOT
 REQUIRE OCP AND IS ONLY REQUIRED TO BE A
 MEANS OF DISCONNECT, RATED FOR THE LOAD
 SERVED,GROUPED AND RATED AS SERVICE
 EQUIPMENT.( NOT SE RATED)
 PLEASE KNOW, AS THE EXISTING MCB SEEMS
 TO BE LOCATED INSIDE AND IS NOT GROUPED
 WITH NEW ATS W/MAIN.
  
 2) NOTE: PLEASE SEE THAT A SLAB DETAIL
 IS REQUIRED AND INDICATING HOW THIS UNIT
 WILL BE ATTACHED TO SLAB.
 NOTES WERE PLACED ON THE SURVEY ON THE
 NEW 8" SLAB, HOWEVER THE SLAB DETAIL IS
 REQUIRED AND HOW THIS UNIT WILL BE
 ATTACHED, ISOLATION PADS ETC?
  
  
 3) NOTE: PLEASE KNOW, ALL NEUTRALS AND
 EQUIPMENT GROUNDSWILL BE REQUIRED TO
 BE SEPARATED IN THE EXISTING PANEL.
 250.6,250.24B.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  