| 2006-06-23 00:00:00 | ********** UNSAT *********** |
| | |
| | 1) NOTE: PLEASE SEE THAT THE SURVEY WITH |
| | "PEN" WRITTEN ON PLANS SHALL BE COPIED |
| | IN TWO SETS. AS PEN AND PENCIL PLANS ARE |
| | NOT PERMITTED UNLESS COPIED. |
| | 106.2.1 |
| | THESE SITE SURVEY PLANS WHICH ALREADY |
| | STMAPED FROM ZONGIN WILL BERE-STAMPED. |
| | |
| | 2) NOTE: PLEASE SEE THAT CONDUIT FROM |
| | METER TO GUTTER SHALL BE REQUIRED TO BE |
| | REMOVED. |
| | |
| | 3) NOTE: PLEASE SEE 250.24B,250.6 AS AN |
| | "EQUIPMENT GROUNDING CONDUCTOR" IS NOT |
| | INSTALLED FROM METER TO THE FIRST MEANS |
| | OF DISCONNECT. |
| | |
| | 4) NOTE: PLEASE SEE NO SPEC/MANUFACTURE |
| | SHEETS WERE SUBMITTED FOR THE ATS. |
| | PLEASE KNOW, AS SHOWN ON RISER THIS ATS |
| | SHALL BE SERVICE ENTRANCE RATED WITH A |
| | MANUAL MEANS OF DISCONNECT RATED FOR THE |
| | LOAD SERVED TO DISCONNECT POWER FROM |
| | FPL. |
| | 230.70,230.2,230.72,230.76,230.79 |
| | PLEASE ALSO SEE MISSING DISC RATED FOR |
| | THE LOAD SERVED FOR THE FEEDERS FROM |
| | GEN 225.31-225.39 |
| | |
| | 5) NOTE: PLEASE SEE BUILDING REVIEW |
| | COMMENTS AS NO SLAB DETAIL WAS |
| | SUBMITTED. |
| | |
| | 6) NOTE: PLEASE BE SURE THE ELECTRICAL |
| | CONT/PERSON RESPONSIBLE FOR PLANS AND |
| | DESIGN SHALL PRINT AND SIGN NAMES ON |
| | PLANS. |
| | 106.2.1 FBC ADMIN SEC. |
| | |
| | 7) NOTE: PLEASE BE SURE ALL SPECS ARE |
| | HIGHLIGHTED FOR MODELS BEING INSTALLED |
| | PLEASE SEE THAT MANUFACTURES SHEETS |
| | SHALL CLEARLY INDICAT ETH MIN CLEARENCES |
| | REQUIRED FOR EQUIPMENT. |
| | 110.3, 215.5 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |