Plan Review Notes
Plan Review Notes For Permit 06060492
Permit Number 06060492
Review Stop E
Sequence Number 2
Notes
Date Text
2006-07-15 00:00:00** REDLINED **
  
 1) AS SD'S ARE NOT CIRCUITED AS
 PERVIOUSLY NOTED, PLEASE BE SURE ARC
 FAULT PROTECTION IS PROVIDED AS REQUIRED
 UNDER THE 2002 NEC 210.12B.
 THESE MAY BE CIRCUITED TO BEDRM(S)
 CIRCUITS.
  
 2) MAIN ELECTRICAL PANEL SHALL FACE THE
 MAIN HALL WAY AND MAY NOT FACE BATH RM.
 SHALL ALSO MEET ALL CLEARNCES PER
 110.26, 240.24, 408.7.
  
 THE ABOVE HAS BEEN REDLINED AND AND NO
 REVISIONS ARE REQUIRED AT THIS TIME.