| Plan Review Notes For Permit 06060492 |
| Permit Number |
06060492 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-07-15 00:00:00 | ** REDLINED ** | | | | | | 1) AS SD'S ARE NOT CIRCUITED AS | | | PERVIOUSLY NOTED, PLEASE BE SURE ARC | | | FAULT PROTECTION IS PROVIDED AS REQUIRED | | | UNDER THE 2002 NEC 210.12B. | | | THESE MAY BE CIRCUITED TO BEDRM(S) | | | CIRCUITS. | | | | | | 2) MAIN ELECTRICAL PANEL SHALL FACE THE | | | MAIN HALL WAY AND MAY NOT FACE BATH RM. | | | SHALL ALSO MEET ALL CLEARNCES PER | | | 110.26, 240.24, 408.7. | | | | | | THE ABOVE HAS BEEN REDLINED AND AND NO | | | REVISIONS ARE REQUIRED AT THIS TIME. |
|