Plan Review Notes
Plan Review Notes For Permit 06060492
Permit Number 06060492
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-13 00:00:00*********UNSAT ************
  
 1) NOTE: PLEASE SEE PLANS INDICATE THE
 2001 FBC. PLEASE KNOW, AS OF OCT 1ST,
 2005, FLORIDA ADOPTED THE 2004 FBC.
 PLEASE SEE THE FOLLOWING CODES SHALL
 ALSO BE REFERENCED ON PLANS AT A MIN.
 2002 NFPA-72, 2002 NFPA-70, NFPA-101
 2003.
  
 2) NOTE: PLEASE SEE PANEL LOCATION AS
 SHOWN IS NOT PERMITTED AND DOES NOT MEET
 110.26,408.7,240.24 ETC.
 PLEASE RELOCATE.
  
 3) NOTE: PLEASE VERIFY SD'S ARE SHOWN.
 PLEASE INDICATE IF THESE ARE 120V W/
 BATTERY BACK AND CIRCUITING.
 PLEASE SEE SD'S ARE MISSING OUTSIDE
 BEDRMS. IF WITHIN 20' OF COOKING
 APPLIANCES,THEN SD'S SHALL BE OF A
 RE-SETTING TYPE OR PHOTOELECTRIC EYE
 TYPE.
 NFPA-72 11.5.1.1, 11.5.3.5,
 FBC R313
  
 4) NOTE: PLEASE SEE THE CIRCUITS IN
 PANEL SCHEDULE LABELED AS GEN LTS AND
 GEN RECEPTS SHALL BE SPECIFIC TO THE
 LOCATIONS IN WHICH THEY FEED.
 408.4.
 IE: MAST BEDRM LTS, KITCHEN LTS, BEDRM
 #2 RECETPS ETC.
  
 5) NOTE: PLEASE SEE POSSIBEL MISSIGN
 RECEPT PER 210.52 IN BEDRM.
 REDLINED.
  
  
 **PLEASE BE SURE TO SEE ANY COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** WHEN RESUBMITTING PLANS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 SUBMIT ONLY ONE COPY OF THE OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  