| 2006-06-13 00:00:00 | *********UNSAT ************ |
| | |
| | 1) NOTE: PLEASE SEE PLANS INDICATE THE |
| | 2001 FBC. PLEASE KNOW, AS OF OCT 1ST, |
| | 2005, FLORIDA ADOPTED THE 2004 FBC. |
| | PLEASE SEE THE FOLLOWING CODES SHALL |
| | ALSO BE REFERENCED ON PLANS AT A MIN. |
| | 2002 NFPA-72, 2002 NFPA-70, NFPA-101 |
| | 2003. |
| | |
| | 2) NOTE: PLEASE SEE PANEL LOCATION AS |
| | SHOWN IS NOT PERMITTED AND DOES NOT MEET |
| | 110.26,408.7,240.24 ETC. |
| | PLEASE RELOCATE. |
| | |
| | 3) NOTE: PLEASE VERIFY SD'S ARE SHOWN. |
| | PLEASE INDICATE IF THESE ARE 120V W/ |
| | BATTERY BACK AND CIRCUITING. |
| | PLEASE SEE SD'S ARE MISSING OUTSIDE |
| | BEDRMS. IF WITHIN 20' OF COOKING |
| | APPLIANCES,THEN SD'S SHALL BE OF A |
| | RE-SETTING TYPE OR PHOTOELECTRIC EYE |
| | TYPE. |
| | NFPA-72 11.5.1.1, 11.5.3.5, |
| | FBC R313 |
| | |
| | 4) NOTE: PLEASE SEE THE CIRCUITS IN |
| | PANEL SCHEDULE LABELED AS GEN LTS AND |
| | GEN RECEPTS SHALL BE SPECIFIC TO THE |
| | LOCATIONS IN WHICH THEY FEED. |
| | 408.4. |
| | IE: MAST BEDRM LTS, KITCHEN LTS, BEDRM |
| | #2 RECETPS ETC. |
| | |
| | 5) NOTE: PLEASE SEE POSSIBEL MISSIGN |
| | RECEPT PER 210.52 IN BEDRM. |
| | REDLINED. |
| | |
| | |
| | **PLEASE BE SURE TO SEE ANY COMMENTS |
| | FROM OTHER TRADES WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** WHEN RESUBMITTING PLANS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS FROM SETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | SUBMIT ONLY ONE COPY OF THE OLD/VOIDED |
| | SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |