| Plan Review Notes For Permit 06060451 |
| Permit Number |
06060451 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-07-03 00:00:00 | ******DENIED 2ND TIME****** | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR GAS RESUBMITTAL: | | | | | | 1. THE MANUFACTURE CUT SHEETS SUBMITTED | | | FOR THE GAS REGULATORS FOR THE | | | RESUBMITTAL ARE FOR LP GAS, NOT NATURAL | | | GAS AS THE DRAWING INDICATES. PLEASE SEE | | | ATTACHED APPROVED NATURAL GAS REGULATOR | | | APPROVED AND SUGGESTED FOR USE ON 2LP | | | NATURAL GAS SYSTEMS BY FLORIDA PUBLIC | | | UTILITIES COMPANY, THE AMERICAN METER | | | MODEL #1813. | | | 2. A SEDIMENT TRAP IS REQUIRED PER | | | FBC-2004, SEC. 408.4. | | | 3. A SHUT OFF VALVE SHALL BE INSTALLED | | | IMMEDIATELY AHEAD OF EACH MP REGULATOR | | | PER FBC-2004, SEC. 409.4. | | | | | | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN | | | RESUBMITTING, PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|