Date Text
2006-07-03 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS RESUBMITTAL:
  
 1. THE MANUFACTURE CUT SHEETS SUBMITTED
 FOR THE GAS REGULATORS FOR THE
 RESUBMITTAL ARE FOR LP GAS, NOT NATURAL
 GAS AS THE DRAWING INDICATES. PLEASE SEE
 ATTACHED APPROVED NATURAL GAS REGULATOR
 APPROVED AND SUGGESTED FOR USE ON 2LP
 NATURAL GAS SYSTEMS BY FLORIDA PUBLIC
 UTILITIES COMPANY, THE AMERICAN METER
 MODEL #1813.
 2. A SEDIMENT TRAP IS REQUIRED PER
 FBC-2004, SEC. 408.4.
 3. A SHUT OFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR
 PER FBC-2004, SEC. 409.4.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  