Plan Review Notes
Plan Review Notes For Permit 06060449
Permit Number 06060449
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-06 00:00:00******* UNSAT2ND REVIEW ********
  
 ** PLEASE SEE SOME COMMENTS REMAIN AND
 SOME ARE NEW DUE TO CHANGES ON PLANS.
  
  
 1) NOTE: OK.
  
 2) NOTE: NO, ? PLEASE SEE RISER NOW
 INDICATES SE RATED ATS, WHICH ARE NOW
 NOT REQUIRED AS NEW MAINS ARE BEING
 SHOWN IN FRONT OF THEESE ATS'S>??
 PLEASE VERIFY.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT THE ATS AS
 SHOWN MUST BE "SERVICE ENTRANCE RATED,
 CONTAING A MANUAL MEANS OF DISCONNECT
 RATED FOR THE LOAD SERVED ETC
 230.70,230.76,230.79
  
 3) NOTE: NO, PLEASE SEE THIS IS NOT
 DONE. PLEASE SEE NO DISCONNECT MEANS FOR
 FEEDERS FROM GEN ARE SHOWN. THE ATS
 UNITS SHOWN ONLY DISCONNECT POWER FROM
 THE NORMAL SIDE AND NOT EM FEEDERS. THE
 DISCONNECTING MEANS MUST BE RATED FOR
 THE LOAD SERVED. DOES NOT REQUIRE OCP.
 ONLY DISCONNECTING MEANS. PLEASE SEE
 COMMENT ABOVE AT THE ATS UNITS NEED ONLY
 RATED FOR "SERVICE EQUIPMENT" IF MAINS
 ARE LOCATED IN FRONT OF THESE ATS'S.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING DISCONNECT
 FOR FEEDERS FROM GEN.
 225.31-225.39
  
 4) NOTE: NO, REPSONSE MENTIONS THIS IS
 DONE, HOWEVER NOT ON RISER.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE OCP AT GEN
 ON RISER.
 215.5.
  
 5) NOTE: SAME, THIS IS DONE BUT LEFT IN
 AS COMMENT AS ATS AND OR GEN MAY CHANGE.
 PLEASE SEE THAT SPECS SHALL BE
 "HIGHLIGHTED" FOR THE GEN TO BE
 INSTALLED.
 215.5
  
 6) NOTE: NO, PLEASE SEE MIN CLEARENCES
 ARE SHOWN AS 3FT YET, DARWN AND SHOWN AS
 18"?? PLEASE KNOW, AS ZONING REQUIRES
 "X" DISTANCE FROM PROPERTY LINE AND GEN
 IS REQUIRED TO BE 3' FROM HOUSE, A NEW
 LOCATION FOR GEN MUST BE CHOSEN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT THE GEN
 LOCATION AS SHOWN DOES NOT APPEAR IT
 WILL BE PERMITTED TO BE INSTALLED THIS
 CLOSE TO THE HOUSE.
 PLEASE KNOW, BASED ON ZOING REQUIREMENTS
 AND THE WIDTH OF THE GEN, THE DISTANCE
 OFF THE WALL OF THE HOUSE MAY BE AN
 ISSUE.
 ALL CLEARENCES SHALL BE INDICATED FROM
 HOUSE, WALL, ETC
 PLEASE SEE MECH COMMENTS AND PLEASE ALSO
 BE SURE THE MANUFACTURES SPECS/CUT
 SHEETS INCLUDE THE MIN CLEARENCES AROUND
 EQUIPMENT.
 215.5
  
 7) NOTE: OK.
  
 8) NOTE:NO, RESPONSE MENTIONS
 112A'S.THIS IS NOT THE AIC RATINGS AS
 REQUIRED.110.9,702.5 ETC
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT.
  
 9) NOTE: OK, AS NEW RISER WAS DRAWN. SEE
 ANY NEW COMMENTS.
  
 10)NOTE: OK.
  
 11) NOTE: NO, PLEASE SEE THAT ALL
 CONDUCTORS ARE REQUIRED TO BE SHOWN. THE
 NUMBER, THE SIZES, THE EQUIPMENT
 GROUNDINGETC .
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE ALL CONDUCTORS
 IN RACEWAYS, INCLUDING EQUIPMENT
 GROUNDING CONDUCTORS.
 250.110,250.24B,250.122,240.4,310.16
  
 ** NEW NOTE **
  
 12) NOTE: PLEASE SEE FS 553.80(2)(B)
 WITH RESPECT TO DESIGNER AND REPEAT CODE
 COMPLIANT COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 13) NOTE: PLEASE SEE AHU'S ARE BEING
 NOTED AS 4KW AND THEN DE-RATED AT 65%.
 PLEASE SEE 4KW IS NOT A COMMON OR KNOWN
 HEAT SIZE.
 PLEASE PROVIDE INFORMATION ON HEAT AND
 FIGURE INTO CALCS OR PLEASE KNOW, LOAD
 SHEDDING MAY BE AN OPTION. IF SHEDDING
 A/C HEAT, PLEASE PROVIDE DETAIL ON HOW
 THIS WILL BE DONE.
 LOAD AS SHOWN TAKES LOAD VERY CLOSE TO
 OVERLOAD OF EQUIPMENT.
 EQUIPMENT SHALL BE SIZED TO CARRY THE
 INTENDED LOAD.
 702.5
  
 14) NOTE: PLEASE KNOW ALL PLANS/DESIGNS
 AND LOAD CALCS SHALL CONTAIN THE PRINTED
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR SAID PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  