Plan Review Notes
Plan Review Notes For Permit 06060449
Permit Number 06060449
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-23 00:00:00******* UNSAT ********
  
  
 1) NOTE: PLEASE SEE THAT THE LINE AND
 LOAD OF THE SEC'S AND FEEDERS MAY NOT
 OCCUPY THE METER ENCLOSURE.
 230.7 ETC.
  
 2) NOTE: PLEASE SEE THAT THE ATS AS
 SHOWN MUST BE "SERVICE ENTRANCE RATED,
 CONTAING A MANUAL MEANS OF DISCONNECT
 RATED FOR THE LOAD SERVED ETC
 230.70,230.76,230.79
  
 3) NOTE: PLEASE SEE MISSING DISCONNECT
 FOR FEEDERS FROM GEN.
 225.31-225.39
  
 4) NOTE: PLEASE INDICATE THE OCP AT GEN
 ON RISER.
 215.5.
  
 5) NOTE: PLEASE SEE THAT SPECS SHALL BE
 "HIGHLIGHTED" FOR THE GEN TO BE
 INSTALLED.
 215.5
  
 6) NOTE: PLEASE SEE THAT THE GEN
 LOCATION AS SHOWN DOES NOT APPEAR IT
 WILL BE PERMITTED TO BE INSTALLED THIS
 CLOSE TO THE HOUSE.
 PLEASE KNOW, BASED ON ZOING REQUIREMENTS
 AND THE WIDTH OF THE GEN, THE DISTANCE
 OFF THE WALL OF THE HOUSE MAY BE AN
 ISSUE.
 ALL CLEARENCES SHALL BE INDICATED FROM
 HOUSE, WALL, ETC
 PLEASE SEE MECH COMMENTS AND PLEASE ALSO
 BE SURE THE MANUFACTURES SPECS/CUT
 SHEETS INCLUDE THE MIN CLEARENCES AROUND
 EQUIPMENT.
 215.5
  
 7) NOTE: PLEASE SEE THAT PERMIT
 APPLICATION SHALL INCLUDE THE GEN TO BE
 INSTALLED.
  
 8) NOTE: PLEASE INDICATE AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT.
  
 9) NOTE: PLEASE SEE SERVICE SEEMS TO BE
 400A AND BOTH PANELS ARE SHWON BEING FED
 FROM THE 200A ATS. HOW IS THIS POSSIBLE
 WHEN BOTH PANELS EXISTING ARE 200A AS
 INDICATED BY THE CONDUCTORS SIZES.
 PLEASE SEE SPECS AS SHOWN WILL NOT BE
 ABLE TO BE USED.
  
 10)NOTE: PLEASE SEE THE ELEC CONT DID
 NOT SIGN ON THE ELECTRICAL LINE ON
 APPLICATION FOR THE ELECTRICAL PERMIT.
 IF THIS IS THE INTENT, PLEASE DO SO WHEN
 RESUBMITTING PLANS. IF THERE ARE ANY
 QUESTIONS, ON THIS PLEASE CALL.
  
 11) NOTE: PLEASE INCLUDE ALL CONDUCTORS
 IN RACEWAYS, INCLUDING EQUIPMENT
 GROUNDING CONDUCTORS.
 250.110,250.24B,250.122,240.4,310.16
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  