| 2006-06-23 00:00:00 | ******* UNSAT ******** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THAT THE LINE AND |
| | LOAD OF THE SEC'S AND FEEDERS MAY NOT |
| | OCCUPY THE METER ENCLOSURE. |
| | 230.7 ETC. |
| | |
| | 2) NOTE: PLEASE SEE THAT THE ATS AS |
| | SHOWN MUST BE "SERVICE ENTRANCE RATED, |
| | CONTAING A MANUAL MEANS OF DISCONNECT |
| | RATED FOR THE LOAD SERVED ETC |
| | 230.70,230.76,230.79 |
| | |
| | 3) NOTE: PLEASE SEE MISSING DISCONNECT |
| | FOR FEEDERS FROM GEN. |
| | 225.31-225.39 |
| | |
| | 4) NOTE: PLEASE INDICATE THE OCP AT GEN |
| | ON RISER. |
| | 215.5. |
| | |
| | 5) NOTE: PLEASE SEE THAT SPECS SHALL BE |
| | "HIGHLIGHTED" FOR THE GEN TO BE |
| | INSTALLED. |
| | 215.5 |
| | |
| | 6) NOTE: PLEASE SEE THAT THE GEN |
| | LOCATION AS SHOWN DOES NOT APPEAR IT |
| | WILL BE PERMITTED TO BE INSTALLED THIS |
| | CLOSE TO THE HOUSE. |
| | PLEASE KNOW, BASED ON ZOING REQUIREMENTS |
| | AND THE WIDTH OF THE GEN, THE DISTANCE |
| | OFF THE WALL OF THE HOUSE MAY BE AN |
| | ISSUE. |
| | ALL CLEARENCES SHALL BE INDICATED FROM |
| | HOUSE, WALL, ETC |
| | PLEASE SEE MECH COMMENTS AND PLEASE ALSO |
| | BE SURE THE MANUFACTURES SPECS/CUT |
| | SHEETS INCLUDE THE MIN CLEARENCES AROUND |
| | EQUIPMENT. |
| | 215.5 |
| | |
| | 7) NOTE: PLEASE SEE THAT PERMIT |
| | APPLICATION SHALL INCLUDE THE GEN TO BE |
| | INSTALLED. |
| | |
| | 8) NOTE: PLEASE INDICATE AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT. |
| | |
| | 9) NOTE: PLEASE SEE SERVICE SEEMS TO BE |
| | 400A AND BOTH PANELS ARE SHWON BEING FED |
| | FROM THE 200A ATS. HOW IS THIS POSSIBLE |
| | WHEN BOTH PANELS EXISTING ARE 200A AS |
| | INDICATED BY THE CONDUCTORS SIZES. |
| | PLEASE SEE SPECS AS SHOWN WILL NOT BE |
| | ABLE TO BE USED. |
| | |
| | 10)NOTE: PLEASE SEE THE ELEC CONT DID |
| | NOT SIGN ON THE ELECTRICAL LINE ON |
| | APPLICATION FOR THE ELECTRICAL PERMIT. |
| | IF THIS IS THE INTENT, PLEASE DO SO WHEN |
| | RESUBMITTING PLANS. IF THERE ARE ANY |
| | QUESTIONS, ON THIS PLEASE CALL. |
| | |
| | 11) NOTE: PLEASE INCLUDE ALL CONDUCTORS |
| | IN RACEWAYS, INCLUDING EQUIPMENT |
| | GROUNDING CONDUCTORS. |
| | 250.110,250.24B,250.122,240.4,310.16 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |