3 |
|
| Notes |
| Date |
Text |
| 2007-09-06 15:45:46 | REVISED PLANS. | | | | | | SPACING FOR KITCHEN COUNTER SPACE DOES NOT APPEAR TO | | | MEET 210.52C1, THIS IS TO BE VIF. | | | NEW ENGINEER OF RECORD. LTRS SUBMITTED. | | | | | | ** REDLINED CIRCUIT FOR KITCHEN AS PLANS INDICATE #5 | | | FOR SMALL APPLIANCE WHEN #5 ON SCHEDULE IS ONE PHASE OF | | | THE RANGE. | | | THIS SHOULD BE CIRCUIT #10 |
|