Plan Review Notes
Plan Review Notes For Permit 06060344
Permit Number 06060344
Review Stop E
Sequence Number 3
Notes
Date Text
2007-09-06 15:45:46REVISED PLANS.
  
 SPACING FOR KITCHEN COUNTER SPACE DOES NOT APPEAR TO
 MEET 210.52C1, THIS IS TO BE VIF.
 NEW ENGINEER OF RECORD. LTRS SUBMITTED.
  
 ** REDLINED CIRCUIT FOR KITCHEN AS PLANS INDICATE #5
 FOR SMALL APPLIANCE WHEN #5 ON SCHEDULE IS ONE PHASE OF
 THE RANGE.
 THIS SHOULD BE CIRCUIT #10