| 2007-07-16 10:53:37 | REV FOR FINAL. | | | CHANGED THE ELECTRICAL ENGINEER OF RECORD. LTR FOR | | | CHANGE SUBMITTED. | | | | | | REDLINED LOAD FOR SMALL APPL ON PANEL SCHEDULE. SHOWS | | | 450VA WHEN THIS SHOULD BE 1500VA AS STATED ON LOAD | | | CALCULATIONS. | | | | | | REDLINED BATH RECEPT, VIF 210.52D. RECEPTACLE IS SHOWN | | | AS EXISTING, HOWEVER IF VANITY IS NEWLY LOCATED, GFI IS | | | TO BE WITHIN 3FT OF LAV. |
|