| Plan Review Notes For Permit 06060329 |
| Permit Number |
06060329 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-07-23 10:20:22 | *** UNSAT *** | | | | | | | | | 1) NOTE: PLEASE SEE THE LOADS AND CIRCUITS FOR ONE OR | | | MORE OF THE SMALL APPLIANCE CIRCUITS INCLUDING DINING | | | ROOM ARE TO BE SHOWN AND FIGURED AT 1500VA PER | | | 210.52B1, 210.11C1, 220.16 | | | PLEASE BE SURE TO ADJUST BOTH THE PANEL SCHEDULE AND | | | LOAD CALCULATIONS. | | | PLEASE SEE PLANS ARE MISSING THE SMALL APPLIANCE | | | CIRCUITS AS WELL AS PANEL SCHEDULE AS REQUIRED. | | | | | | 2) NOTE: PLEASE SEE NFPA-72, THE SMOKE DEVICES ARE | | | SHOWN AS SMOKE DETECTORS, YET THESE SEEM TO BE SMOKE | | | ALARMS. PLEASE SEE DEFINITIONS FOR THESE DEVICES UNDER | | | NFPA-72. | | | PLEASE ADJUST AS PLANS ARE COMING BACK FOR OTHER | | | COMMENTS. | | | | | | 3) NOTE: PLEASE BE SURE TO SUBMIT LETTERS WHICH ARE | | | ATTACHED TO PLANS WHEN RESUBMITTING. | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|