| 2007-06-08 20:21:09 | ** UNSAT* |
| | |
| | 1) NOTE: PLEASE SUBMIT REVISED ELECTRICAL PLANS SHOWING |
| | REVISIONS. PLEASE SUBMIT REVISED PANEL SCHEDULE FOR |
| | CIRCUITS TO BE SPECIFIC TO ALL AREAS AND ROOMS IN WHICH |
| | THEY FEED. PLEASE SEE 408.4 |
| | |
| | 2) NOTE: PLEASE COORDINATE ALL ARCHITECTURAL, |
| | ELECTRICAL, MECHANICAL AND PLUMBING SHEETS AS PANELS |
| | ARE NOT THE SAME ON SHEETS. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE A SHEETS INDICATE A STACKED |
| | WASHER/DRYER HOWEVER ELECTRICAL PANEL SCHEDULE |
| | INDICATES THESE AS SEPARATE UNITS? |
| | PLEASE ADJUST A SHEETS OR ELECTRICAL PLANS AND PANEL |
| | SCHEDULE. |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE THE CONDUCTORS FOR EACH AHU IS NOT |
| | OF SUFFICIENT SIZE PER 310.16. REQUIRES #6 MINIMUM FOR |
| | 60AMP BREAKER. |
| | |
| | 5) NOTE: PLEASE SEE PLANS SEEM TO SHOW A GUTTER OR |
| | J-BOX OUTSIDE, THIS SEEMS TO BE AN OLD CT CAN WHICH IS |
| | BEING REQUIRED TO BE REMOVED BASED ON FIELD CONDITIONS |
| | AND PICTURES SUBMITTED TO THIS OFFICE FROM THE |
| | ELECTRICAL INSPECTOR. |
| | PLEASE BE SURE THE ON-SITE WORK IS COORDINATED WITH |
| | PLANS. |
| | |
| | 6) NOTE: PLEASE SUBMIT REVISED ENERGY CALCULATIONS |
| | BASED ON FIELD CHANGES. PLEASE SEE 13-415.1.AB.1.1, |
| | 13-415.2.ABC.1.2 ETC. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |