| Date |
Text |
| 2006-06-13 00:00:00 | *************** UNSAT ************* |
| | |
| | ** PLEASE KNOW, PLANS ARE NOT COMPLETE |
| | AT THIS TIME. |
| | |
| | |
| | 1) NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH A PANEL |
| | SCHEDULE TO BE SUBMITTED. |
| | 215.5 |
| | |
| | 2) NOTE: PLEASE SEE THAT NO PANEL |
| | SCHEDULE WAS SUBMITTED SHOWING ALL MIN |
| | CIRCUITS, LOADS, CONDUCTOR SIZES ETC. |
| | 215.5,408.4, 310.16,240.4 ETC |
| | |
| | 3) NOTE: PLEASE SUBMIT COMPLETE LOAD |
| | CALCULATIONS AND RISER SHOWING THE |
| | EXISTING SERVICE, SIZES OF EQQUIPMENT |
| | ETC. 220.3,220.10,220.11,220.13, ALL |
| | CONTINOUS LOADS @125% PER 215.3,230.42 |
| | ETC |
| | 215.5.240.4.310.16 ETC. |
| | |
| | 4) NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUTING OF ALL EM/ EXT LTS. |
| | |
| | 5) NOTE: PLEASE INDICATE NEW OR EXISTING |
| | SIGN CIRCUIT REQUIRED PER 600.5 |
| | |
| | 6) NOTE: PLEASE SEE BUILDING SEEMS TO BE |
| | PART OF A LARGER STRUCTURE. IF THE |
| | BUILDING IS LARGER THAN 5000 SA FT OVER |
| | ALL, THEN PLEASE SEE FBC CHAPTER |
| | 13,13-415.1.ABC.1.1, .1.2,.1.3. |
| | PLEASE PROVIDE LIGHTING CONTROLS WHICH |
| | ARE REQUIRED UNDER THE NEW FLORIDA |
| | ENERGY CODE. |
| | |
| | 7) NOTE: PLEASE SEE PANEL AS SHOWN ON |
| | PLANS DOES NOT MEET 110.26,240.24. |
| | PLEASE ADJUST. |
| | |
| | 8) NOTE: PLEASE SEE LOCATION OF WATER |
| | HEATER DOES NOT MIN CLEARENCES PER |
| | 422.17 |
| | PLEASE ADJUST. |
| | |
| | 9) NOTE: PLEASE SEE POSSIBLE NOTES FROM |
| | BUILDING REVIEW FOR VALUATION OF PROJECT |
| | PER FBC 108.3 ADMINISTRATIVE SECTION AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | |
| | 10) NOTE: PLEASE SEE THE OWNER AS SIGNED |
| | ON NOTICE OF COMMENCEMENT IS DIFFERENT |
| | THAN THE OWNER AS LISTED IN OUR SYSTEM |
| | AND THE PROPERTY APPRAISER'S OFFICE. |
| | PLEASE PROVIDE DOCUMENTS FOR NEW |
| | OWNERSHIP. |
| | FS 713.13 |
| | |
| | 11) NOTE: PLEASE SEE THAT THE CODES IN |
| | EFFECT SHALL BE STATED ON PLANS. 106.1.2 |
| | PLEASE SEE PLANS SHALL INCLUDE AT A MIN |
| | 2004 FBC, NFPA-72 2002 , NFPA-101 2003, |
| | NFPA-70 2002 . |
| | PLEASE SEE OTHER CODES MAY BE REQUESTED |
| | BY OTHER REVIEWER(S). |
| | |
| | 12) NOTE: PLEASE VERIFY WHAT TYPE OF |
| | EGRESS LIGHTING IS PROVIDED TO THE |
| | PUBLIC RIGHT OF WAY PER LS101 7.8,7.9 |
| | NO LIGHTING INDICATED AT THIS TIME. |
| | |
| | ** PLEASE KNOW, PLANS MAY HAVE FURTHER |
| | COMMENTS AS PLANS WERE NOT COMPLETE AT |
| | THIS TIME. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |