| 2006-06-09 00:00:00 | | | | *****TO KEN CONRAD FOR PRE-INSPECT***** | | | | | | DENIED | | | | | | 1) ROOF PRODUCT HAS MAX DESIGN PRESSURE | | | OF -85PSF WITHOUT MEAN ROOF HT., | | | BUILDING SIZE, ETC. COMPLIANCE WITH THE | | | WIND LOAD CANNOT BE CALCULATED. UNDER | | | LIMITATIONS ON PAGE 4 OF THE NOA ANY | | | INCREASE IN THE DESIGN PRESSURES FOR | | | CORNERS SHALL BE CALCULATED BY A DESIGN | | | PROFESSIONAL. | | | | | | 2) A GENERAL CONTRACTOR CANNOT INSTALL | | | ROOFING OTHER THAN THAT PROVIDED UNDER | | | EXECUTIVE ORDER 06-83 THAT EXPIRES | | | 6/12/06 WHICH ALLOWS A CGC TO INSTALL | | | WOOD SHINGLES AND SHAKES OR ASPHALT AND | | | FIBERGLASS SHINGLES.PER 489.113(3)B&G | | | | | | 3) DRAWING SHOWS MUCH MORE THAN ROOFING | | | BEING PERFORMED,(NEW PILASTER AND TIE | | | BEAM, STRUCTURAL STEEL,ETC.) AS SUCH A | | | PRE-INSPECTION IS WARRANTED AND FURTHER | | | PLANS MAY BE REQUIRED TO COVER SCOPE OF | | | WORK BEING PERFORMED | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|