Plan Review Notes
Plan Review Notes For Permit 06060101
Permit Number 06060101
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-08-02 00:00:00*******DENIED***************************
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED AND SHALL BE MOUNTED AT
 DISTANCES NOT TO EXCEED 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 3) AUDIBLE/VISUAL DEVICES REQUIRED FOR
 DUCT SMOKE DETECTORS. IF SPACE HAS FIRE
 ALARM SYSTEM, DETECTORS SHALL INITAITE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 4) SEPARATE SHOP DRAWINGS AND PERMIT
 APPLICATIONS ARE REQUIRED FOR FIRE ALARM
 AND FIRE SPRINKLER REMODEL.
  
 PLEASE ADDRESS THESE COMMENTS AND
 RE-SUBMIT FOR APPPROVAL. IF YOU HAVE ANY
 QUESTIONS PLEASE FEEL FREE TO CONTACT
 THIS OFFICE AT 561-804-4754
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL