| Plan Review Notes For Permit 06060101 |
| Permit Number |
06060101 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-14 00:00:00 | DENIED; | | | 1.GENERAL NOTES #2; DELETE THE WORDS | | | "AIR CHAMBERS" FOR WATER HAMMER | | | ARRESTORS TO BE INSTALLED PER FBC-2004 | | | PLUMBING SEC. 604.9. | | | 2.PAGE M-2, LANDLORD COMMENTS - PLUMBING | | | NOTE#5 FLOOR DRAINS REQUIRED IN | | | BATHROOMS. IF BATHROOMS HAVE FLOOR | | | DRAINS SHOW THEM ON PLANS AS EXISTING, | | | IF NOT PLEASE ADD TO RISER DIAGRAM. | | | 3.PAGE A-6.1 (3) ELEVATION; PLEASE SHOW | | | DIMENTIONS REQUIRED TO MEET FBC-2004 | | | CHAPTER 11 SECTION 11-4.15.2 THRU | | | 11-4.15.4.4. | | | 4.PLEASE LIST DRINKING FOUNTAIN AND MOP | | | SINK TO BE USED MODEL # AND MANUFACTURE. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | | | | | | | |
|