Plan Review Notes
Plan Review Notes For Permit 06060101
Permit Number 06060101
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-06-16 00:00:00***DENIED***
  
 1) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED AND SHALL BE MOUNTED AT
 DISTANCES NOT TO EXCEED 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE SPRINKLER REMODEL.
  
 3) AUDIBLE/VISUAL DEVICES REQUIRED FOR
 DUCT SMOKE DETECTORS. IF SPACE HAS FIRE
 ALARM SYSTEM, DETECTORS SHALL INITAITE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 4) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722