| Date |
Text |
| 2006-06-14 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE ENERGY COMPLIANCE |
| | FORMS ARE SEALED PHOTO-COPIES OF |
| | DESIGNER'S SIGNATURE. |
| | PLEASE SEE FS 481.221,471.025 WHICH |
| | REQUIRES AN ORIGINAL SIGNATUE. |
| | |
| | 2) NOTE: PLEASE SEE FBC CHAPTER 13 |
| | ,13-415.1ABC.1.1, .1.2,.1.3. |
| | PLEASE SEE THE PANEL SCHEDULE MENTIONS |
| | SOME SORT OF TIME CLOCK, HOWEVER NO |
| | DETAIL SUBMITTED FOR TYPE REQUIRED. |
| | PLEASE ALSO SEE LOCATIONS OF OVER RIDES |
| | COULD NOT BE FOUND. PLEASE ALSO INDICATE |
| | TIME LIMITS FOR DEVICES WHICH ARE |
| | CHOSEN. |
| | |
| | 3) PLEASE SEE COLOR CODING ON NOTE WHICH |
| | MENTIONS 277/480 AS BROWN, ORANGE, |
| | YELLOW. |
| | PLEASE KNOW, A HIGH LEG IS MARKED WITH |
| | ORANGE AND 277/480 SYSTEM DOES NOT |
| | CONTAIN A HIGH LEG. |
| | PLEASE INDICATE AS BR,PURPLE YEL. |
| | 215.5,90.4 |
| | |
| | 4) NOTE: PLEASE SEE THE "LOCK ON" DEVICE |
| | BEING PROPOSED SHALL HAVE THE DEVICE |
| | USED FOR "LOCKING" A PERMANANT PART OF |
| | THE BREAKER. THE DEVICE CAN NOT BE A |
| | CLIP/SNAP ON TYPE AND IS NOT ACCEPTABLE |
| | TO THIS AHJ. PLEASE KNOW, IF THE BREAKER |
| | DOES NOT COME FROM THE MANUFACTURE WITH |
| | THE DEVICE MADE ONTO THE BREAKER, THEN |
| | EM/EXT LTS DO NOT MEET THE EXCEPTIONS |
| | SETFORTH ON 700.12EXPT AND ALL EM / EXT |
| | LTS SHALL BE CIRCUITED AHEAD OF LOCAL |
| | SWITCH FOR LOCAL LIGHTING IN ANY ONE |
| | AREA. |
| | |
| | 5) NOTE: PLEASE PROVIDE LOAD |
| | CALCUALTIONS,AND PLEASE INDICATE THE |
| | CONTINUOUS LOADS AT 125%. |
| | 215.3,230.42,220.3,220.10,220.11,220.13, |
| | ETC |
| | PLEASE SEE TRK CALCUALTIONS SHALL BE |
| | SHOWN FOR LIN FT ETC. |
| | 220.12 |
| | |
| | ** IMPROTANT** |
| | WHEN RESUBMITING PLANS ONCE ALL REVIEWS |
| | ARE COMPLETED, PLEASE COMPLETELTY |
| | REMOVED ANY OLD/VOIDED SHEETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | PLEASE ONLY SUBMIT ONE COPY OF THE |
| | OLD/VOIDED SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |