| 2006-06-12 00:00:00 | ********** UNSAT ************* |
| | |
| | ** PLEASE SEE PLANS ARE ONLY SUBMITTED |
| | FOR "PLAN REVIEW" AND HAVE NOT BEEN |
| | SUBMITTED FOR PERMIT. |
| | |
| | 1) NOTE: PLEASE SEE PLANS SUBMITTED |
| | SEEEM TO HAVE GOTTEN WET AND THE |
| | SIGNATURE FOR THE ARCHITTECT ON BOTH |
| | SETS HAVE BE DISTORTED. |
| | FS481.221 |
| | |
| | 2) NOTE: PLEASE SEE FBC CHAPTER 13, |
| | 13-415.1.ABC.1.1,.1.2,.1.3 |
| | PLEASE PROVIDE AN ACCEPTABLE METHOD, |
| | SCHEDULING , DEVICES AND TIME LIMITS ON |
| | DEVICES BEING USED. |
| | ALL REQUIRED OVER RIDE DEVICE LOCATIONS |
| | SHALL BE INDICATED ON PLANS. |
| | PLEASE SEE ALL SEPARATE SPACES. |
| | |
| | 3) NOTE: PLEASE CLARIFY FEEDERS TO |
| | EXISTING PANEL. RISER SHOWS PARALLEL, |
| | CONDUITS FOR A 400A SERVICE? |
| | IS THE PANEL EXISTING 200A OR 400A? |
| | IS THE EXISTING FEEDER ONE OR TWO 2" |
| | CONDUITS? |
| | 215.5 |
| | |
| | 4) NOTE: PLEASE SEE PLANS ARE INDICATING |
| | DESIGN AND CODES UNDER THE 2001 FBC. |
| | PLEASE KNOW, OCT 1ST, 2005 , THE FBC WAS |
| | CHANGED TO THE 2004 FBC |
| | PLEASE ADJUST PLANS AND CODES REFLECTED. |
| | 215.5 |
| | |
| | 5) NOTE: PLEASE SEE MANY CIRCUITS ON |
| | PANEL SCHEDULE ARE SHOWN AS "EXISTING"?? |
| | HOW IS THIS POSSIBLE WHEN THIS IS A NEW |
| | BUILD OUT OF AN EXISTING SPACE?? |
| | PLEASE CORRLEATE PLANS. |
| | |
| | 6) NOTE: PLEASE SEE 408.4, PANEL |
| | SCHEDULE SHALL INDICATE ALL CIRCUITS |
| | SPECIFIC TO ROOMS AND AREAS. IE; BATH |
| | LTS, OFFICE LTS, OFFICE RECEPTS ETC. |
| | 215.5 |
| | |
| | 7) NOTE: PLEASE PROVIDE LOAD |
| | CALCULATIONS WHICH MEET NEC 220. |
| | 220.3,220.10,220.11,220.13 ETC |
| | AND ALL CONTINUOUS LOADS AT 125%. |
| | 215.5 |
| | |
| | 8) NOTE: PLEASE COMPLETE ALL CIRCUITS ON |
| | PLANS AND CORRELATE WITH THE PANEL |
| | SCHEDULE. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF EM |
| | /EXT LTS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |